2005-01-07 00:00:00 
  
 .PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE OVERCURRENT PROTECTION FOR AHU
 #2 AT 60 AMPS IS TOO LARGE TO PROTECT A
 5KW UNIT.(5000X125%/240=26 AMPS, MAX 30
 AMP OCP). ALSO 60 AMP OCP SHOWN INTHE
 MAIN PANEL SEEM TOOLARGE FOR THE
 CONDENSING UNIT. SEE ARTICLE 440.22
 NEC.
  
 2} THERE ARE NO PROVISIONS IN THE
 CALCULATIONS FOR POOL EQUIPMENT, BUT
 THERE IS EQUIPMENT SHOWN ON THE PLAN.
  
 3} IF NOTE #15 IS ADHERED TO, THOSE
 CIRCUITS WOULD HAVE TO BE PROTECTED BY
 AN AFCI BECAUSE THE DETECTORS ARE
 LOCATED IN BEDROOMS. 210.12.
  
 4} THE GFI'S SHOWN IN THE DINING ROOM
 AND BREAKFAST NOOK, WHILE NOT REQUIRED
 ALTHOUGH PERMISSIBLE, MUST BE INSTALLED
 IF LEFT ON THE PLAN.
  
 5} A RECEPTACLE NEEDS TO BE ADDED TO
 THE
 MASTER BEDROOM TO COMPLY WITH
 210.52(A).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026