2005-01-25 00:00:00 | CHECKLIST: |
| 1-PROVIDE COMPLETE BATHROOM WITH A DOOR |
| THAT ALLOWS 29" MIN. CLEAR OPENING. |
| SECTION 11-11 FBC 2001. |
| |
| 2-SPECIFY ROOF TILE FASTENING. SECTION |
| 104.2.1.1 CITY AMENDMENTS TO FBC 2001. |
| |
| 3-UPDATE TRUSS ANCHOR SCHEDULE. PROVIDE |
| COMPLETE ENGINEERING CALCULATIONS FOR |
| TYPE AND NUMBER OF FASTENERS THAT DIFFER |
| FROM THOSE TESTED AND PUBLISHED BY THE |
| MANUFACTURER TO COMPLY WITH SECTION |
| 1609.4.3 FBC 2001. |
| |
| 4- A) TITLE BLOCK NEEDS NAME OF |
| ARCHITECT SEALING THE PLANS. SEE CHAPTER |
| 61G1-16004 OF F.A.C. |
| B) STATE REGISTRATION NUMBER IS |
| INCORRECT. REVISE AS REQUIRED. |
| |
| 5-PROVIDE COMPLETE DETAIL/SPECS FOR |
| INSTALLATION OF CEILING AT ENTRY AND |
| REAR PORCH. SPECIFY ALL FASTENERS AND |
| SPACING. SEE ASTM C926 AND ASTM C1063. |
| SEC. 2504.2 FBC 2001. |
| |
| 6-OWNER/AGENT TO SIGN AND DATE THE |
| ENERGY CALCULATIONS. |
| |
| 7-PROVIDE FLORIDA OR LOCAL PRODUCT |
| APPROVAL FOR: |
| A) ENTRY DOORS. SEE SIZE ON PLANS. |
| B) FRENCH DOORS. SEE SIZE ON PLANS. |
| C) CONCRETE LINTELS: NEED DADE COUNTY |
| NOA THAT MATCHES ONE SUBMITTED FOR |
| FLORIDA PRODUCT APPROVAL. |
| D) FIXED WINDOWS THAT MEET THE DESIGN |
| PRESSURES CALCULATED ON PLANS. SEE PLANS |
| FOR SIZE AND LOCATION. |
| E) ARABESQUE WINDOW AS SHOWN ON PLANS. |
| |
| 8- A) PROVIDE COMPLETE UL LISTING AND |
| SPECS FOR FIREPLACE. SEC. 2806 FBC |
| 2001. |
| B) PROVIDE APPROVED BBQ SPECS. SECTION |
| 2808 FBC 2001. |
| |
| 9-STORM SHUTTERS: A) KEY PLAN DOESN'T |
| MATCH PLANS. |
| B) REVISED MIN. PANEL SIZE. SEE |
| ENGINEERED DRAWINGS. |
| C) REVISE INTERIOR AND END ZONES. SEE |
| PLANS. |
| D) REVISE DESIGN PRESSURES. SEE PLANS. |
| |
| 10- PROVIDE COMPLETE FRAMING DETAILS FOR |
| ARABESQUE WINDOW. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| |
| 11-OWES $866.23 FOR UPDATED VALUATION. |
| |
| 12-REVISE FOUNDATION NOTE #2 ON SHEET |
| A-2. SEE CHAPTER 19 FBC 2001 FOR PROPER |
| ACI REFERENCE. |
| |
| 13- REVISE CONNECTORS SPECIFIED ON |
| DETAIL 2/A-9. "SEMCO" IS OUT OF |
| BUSINESS. |
| |