Plan Review Notes For Permit 04121830 |
Permit Number |
04121830 |
|
Review Stop |
E |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2005-12-24 00:00:00 | *** PROVISO *** | | | | 1)NOTE: PLEASE CORRELATE RISER FOR SUB | | PANEL "C" WITH PANEL SCHEDULE "B". | | PLEASE SEE PANEL SCHEDULE "B" INDICATE | | 3#6'S AND 1#6 GRND, HOWEVER RISER SHOWS | | 3#4'S AND 1#6 GRND. | | | | PLEASE REVISE BEFORE FINAL ELECTRICAL | | INSPECTION. | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|