Plan Review Notes
Plan Review Notes For Permit 04121830
Permit Number 04121830
Review Stop P
Sequence Number 4
Notes
Date Text
2006-05-22 00:00:00REVISION: AS BUILT SANITARY PLUMBING
 RISER DIAGRAM
  
 ******PROVISO******
 (A) 708.3.4 BASE OF STACK. A CLEANOUT
 SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK
 (B) 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS. NOTE: WASHING
 MACHINE CLEANOUT SHALL BE 4' ABOVE
 FINNISH FLOOR.