Date |
Text |
2005-12-07 00:00:00 | ********* UNSAT *********** |
| |
| 1)NOTE: PLEASE SEE FOUNTAIN PUMP SHOWN |
| WITH 20A OCP ON #14. |
| |
| 2)NOTE: PLEASE CORRELATE PANEL SCHEDULE |
| FOR POOL PANEL AND PANEL "B" WITH RISER |
| DIAGRAM. |
| PLEASE SEE PANEL "B" SHOWS 100A OCP AND |
| #2 TO POOL PANEL. POOL PANEL ON RISER IS |
| SHOWN AS 80A OCP AND #4 AND POOL PANEL |
| SCHEDULE SHOWS 60A ?? |
| 215.5 |
| |
| 3)NOTE: PLEASE SEE WARMING DRAWER SHOWN |
| ON PLANS, YET THIS IS NOT ON PANEL |
| SCHEDULE OR ADDED TO LOAD CALCS. |
| 215.5 |
| |
| 4)NOTE: PLEASE SEE SD IN MASTER BEDRM IS |
| REQUIRED TO BE WITHIN 12"OF THE HIGHEST |
| POINT OF A FLAT CEILING. |
| PLEASE KNOW, IF TRAT CEILING IS 12" OR |
| MORE ABOVE OTHER CEILING IN RM, THE SD |
| WILL BE REQUIRED TO BE LOCATED IN TRAY |
| CEILING AREA. |
| NFPA-72 11.8.3.5 |
| |
| 5)NOTE: PLEASE CORRELATE THE NUMBER OF |
| RECESSED LTS ON PLANS WITH THE # IN LOAD |
| CALCS ETC. |
| PLEASE SEE LOAD CALCS INDICATE A TOTAL |
| OF 84, HOWEVER THERE ARE 125+ |
| PLEASE ADJUST. |
| 220.3B4 |
| |
| 6)NOTE: PLEASE CLARIFY NOTE FOR ALL |
| "OUTLETS " IN BEDRMS TO HAVE ARC FAULT |
| PROTECTION. THIS INCLUDES , SD', FANS, |
| LTS, AND RECEPTS. |
| 2002 NEC 210.12 |
| IT IS KNOWN THAT THE RECEPTS ARE SHOWN |
| AS AFCI, HOWEVER A AFCI RECEPT IS NOT |
| KNOWN TO BE MADE AT THIS TIME. |
| |
| 7)NOTE: PLEASE SHOW LOCATION OF POOL |
| PANEL ON PLANS. |
| 215.5 |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |