Plan Review Notes
Plan Review Notes For Permit 04121830
Permit Number 04121830
Review Stop E
Sequence Number 4
Notes
Date Text
2005-12-07 00:00:00********* UNSAT ***********
  
 1)NOTE: PLEASE SEE FOUNTAIN PUMP SHOWN
 WITH 20A OCP ON #14.
  
 2)NOTE: PLEASE CORRELATE PANEL SCHEDULE
 FOR POOL PANEL AND PANEL "B" WITH RISER
 DIAGRAM.
 PLEASE SEE PANEL "B" SHOWS 100A OCP AND
 #2 TO POOL PANEL. POOL PANEL ON RISER IS
 SHOWN AS 80A OCP AND #4 AND POOL PANEL
 SCHEDULE SHOWS 60A ??
 215.5
  
 3)NOTE: PLEASE SEE WARMING DRAWER SHOWN
 ON PLANS, YET THIS IS NOT ON PANEL
 SCHEDULE OR ADDED TO LOAD CALCS.
 215.5
  
 4)NOTE: PLEASE SEE SD IN MASTER BEDRM IS
 REQUIRED TO BE WITHIN 12"OF THE HIGHEST
 POINT OF A FLAT CEILING.
 PLEASE KNOW, IF TRAT CEILING IS 12" OR
 MORE ABOVE OTHER CEILING IN RM, THE SD
 WILL BE REQUIRED TO BE LOCATED IN TRAY
 CEILING AREA.
 NFPA-72 11.8.3.5
  
 5)NOTE: PLEASE CORRELATE THE NUMBER OF
 RECESSED LTS ON PLANS WITH THE # IN LOAD
 CALCS ETC.
 PLEASE SEE LOAD CALCS INDICATE A TOTAL
 OF 84, HOWEVER THERE ARE 125+
 PLEASE ADJUST.
 220.3B4
  
 6)NOTE: PLEASE CLARIFY NOTE FOR ALL
 "OUTLETS " IN BEDRMS TO HAVE ARC FAULT
 PROTECTION. THIS INCLUDES , SD', FANS,
 LTS, AND RECEPTS.
 2002 NEC 210.12
 IT IS KNOWN THAT THE RECEPTS ARE SHOWN
 AS AFCI, HOWEVER A AFCI RECEPT IS NOT
 KNOWN TO BE MADE AT THIS TIME.
  
 7)NOTE: PLEASE SHOW LOCATION OF POOL
 PANEL ON PLANS.
 215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]