Plan Review Notes
Plan Review Notes For Permit 04121830
Permit Number 04121830
Review Stop P
Sequence Number 2
Notes
Date Text
2005-03-26 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 A) SHT A6 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS, NOR DOES IT
 REFLECT THE FLOOR PLANS.
 1) RISER INDICATES "TO SEPTIC TANK"
 SEPTIC TANKS ARE NOT APPROVED. CITY
 SEWER SYSTEM AVAILABLE.
 2) FOR W/M TRAP TO CONNECT TO STACK
 DOWN LOW AND HAVE A MINIMUM 2' STANDPIPE
 AND THE CLEANOUT SHALL BE 4' ABOVE THE
 FLOOR FOR ACCESS. SECTIONS 1002.1 AND
 708.10.
 3) BIDET TRAP SHALL BE UNDER THE SLAB,
 NOT ABOVE THE FLOOR AS SHOWN. SECTION
 104.2.1.
 4) SINK DOWNSTREAM OF "HIS" BATHROOM IS
 NOT SHOWN ON THE FLOOR PLAN. SECTION
 104.2.1.
 (SEE RED LINE CORRECTIONS ON ONE SET OF
 PLANS).
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]