Plan Review Notes
Plan Review Notes For Permit 04121830
Permit Number 04121830
Review Stop E
Sequence Number 2
Notes
Date Text
2005-03-21 00:00:00*********UNSAT *******
  
 PLEASE SEE NOTES FROM PREVIOUS REVIEW.
  
 1)NOTE: NOTE #1, NO PLEASE CORRELATE
 RISER DIAGRAM AND PANELS.
 PLEASE SEE PANEL "A" IS SHOWN FEEDING
 SUB-PANEL "C" , RISER SHOWS PANEL "B"?
 PLEASE SEE PANEL "C" IS SHOWN AS 80A
 AND RISER SHOWS AS 150A?
 PLEASE SEE RISER MENTIONS FEED FOR SUB
 PANEL WITH 4#12'S ALONG WITH FEEDER??
  
 2)NOTE: PLEASE SEE FOUNTAIN PUMP SHOWN
 AS 2P20 ON #14 AWG.
  
 3)NOTE: PLEASE SEE BLOWER IS SHOWN AS
 GAS FOR POOL??
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]
2005-03-18 00:00:00IN FOR REVIEW. PLANS UNSAT, NOTES TO
 FOLLOW.