Date |
Text |
2005-01-05 00:00:00 | ************** UNSAT *************** |
| |
| 1)NOTE: PLEASE CORRELATE RISER AND |
| PANELS, PANEL "A" SHOWN AS 150A AND |
| 200A |
| ON RISER. |
| PLEASE ALSE SEE PLANS INDICATE A MAIN |
| DISC ON THE OUTSIDE OF DWELLING, YET |
| RISER DOES NOT CONFRIM THIS.? |
| 215.5 |
| |
| 2)NOTE: PLEASE SEE 250.66,310.15B6 FOR |
| MIN SIZE GROUNDING ELECTRODE CONDUCTOR. |
| |
| 1/0 MIN. |
| |
| 3)NOTE: PLEASE SEE PANEL SCHEDULE |
| INDICATES A WHIRLPOOL TUB, HOWEVER, |
| PLANS DO NOT INDICATE ANY GFI FOR THIS |
| AT WHAT APPEARS TO BE WP TUB AT MASTER |
| BATH LOCATION. |
| 215.5 |
| |
| |
| 3)NOTE: SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| UNIT. |
| IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| TO FLOORS ABOVE AND IN THE VICINITY OF |
| BEDROOMS. |
| PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| A MIN OF 3' FROM BATHROOM DOORS AND |
| KITCHENS. |
| ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| PLEASE SEE MISSING REDLINED. |
| |
| 4)NOTE: PLEASE SEE 210.70 FOR REQUIRED |
| LT FOR AHU/ EQUIPMENT IN ATTIC. |
| |
| 5)NOTE: PLEASE SEE MISSING RECEPT(S) |
| PER |
| 210.52 |
| |
| 6)NOTE: PLEASE SEE MISSING GFI RECEPT |
| FOR KITCHEN ISLAND. PER 210.52C2AT |
| LEAST |
| ONE RECEPTACLE OUTLET SHALL BE |
| INSTALLED |
| AT EACH ISLAND COUNTER SPACE WITH A |
| LONG |
| DIMENSION OF 600 MM (24 IN.) OR GREATER |
| AND A SHORT DIMENSION OF 300 MM (12 |
| IN.) |
| OR GREATER. |
| |
| 7)NOTE: PLEASE SEE 220.3B4 AN OUTLET |
| SUPPLYING RECESSED LUMINAIRE(S) |
| [LIGHTING FIXTURE(S)] SHALL BE COMPUTED |
| BASED ON THE MAXIMUM VOLT-AMPERE RATING |
| OF THE EQUIPMENT AND LAMPS FOR WHICH |
| THE |
| LUMINAIRE(S) [FIXTURE(S)] IS RATED. |
| |
| 8)NOTE: PLEASE VERIFY OCP FOR 7.5KW |
| AHU#3, SHOWN AS 60A. ONLY A NOTE: |
| |
| PLEASE SEE ONE SET OF PLANS HAVE BEEN |
| REDLINED FOR AREAS OF NOTES AND |
| LOCATIONS FOR SOME OF THE ITEMS LISTED |
| ABOVE. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO TWO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |