Plan Review Notes
Plan Review Notes For Permit 04121830
Permit Number 04121830
Review Stop B
Sequence Number 1
Notes
Date Text
2005-02-02 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)THE OWNER INFORMATION DOESN'T
 MATCH
 OUR RECORDS.
  
 2.)THE NOC IS EXPIRED, MORE THAN 90
 DAYS WITHOUT COMMENCING WORK,
 FS713.13(2).
  
 3.)A3, THE NOTE REGARDING THE 10# LL
 IS NOT IN COMPLIANCE WITH FBC TABLE
 1604.1.ATTICS WITH STORAGE ARE TO
 HAVE
 A 30# BCLL.ROOF FRAMING PLAN SHOWS
 10#
 FOR STORAGE AREAS (TWO NOTES).
  
 4.)THE FLOOR PLAN SHOWS THE ROOM
 ADJACENT TO THE CABANA AS AN OFFICE,
 ROOF FRAMING PLAN SHOWS IT AS A GUEST
 ROOM.IS THIS AREA THE "GUEST HOUSE"
 REFERRED TO ON THE PLAN?SLEEPING
 ROOMS
 ARE TO HAVE SMOKE DETECTORS IN
 COMPLIANCE WITH FBC 905.2.2.
  
 5.)THE TWO SETS OF PLANS SUBMITTED
 HAVE DIFFERENT SIGNATURES AND DATES.
  
 6.)SHEET T1, CONCRETE UNIT MASONRY, H
 REFERS TO A CODE FOR HVHZ.CITY OF WPB
 IS NOT IN THE HVHZ.PLEASE CORRECT
 REFERENCES (ACI REFERENCES ARE
 DIFFERENT
 FOR HVHZ AS WELL).
  
 7.SHEET T1, WIND LOADS (DESIGN
 PARAMETERS), REFERS TO A STANDARD FOR
 WOOD CONSTRUCTION WHICH I AM UNABLE TO
 LOCATE IN THE FBC.
  
 8.)A6, KNEE WALL ON GIRDER TRUSS,
 REFERS TO HUGHES CONNECTORS.THEY HAVE
 BEEN OUT OF BUSINESS FOR YEARS.
 SPECIFY
 ONLY AVAILABLE PRODUCTS.
  
 9.)A3 (AT GARAGE) REFERS TO AHU
 INSTALLATION DETAIL ON SHEET 9, BUT
 THERE IS NO SHEET 9.
  
 10.) ROUGH CARPENTRY NOTES (U), SHEET
 T1, SPECIFIES 5/8" PLYWOOD WHICH
 CONFLICTS WITH THE DETAILS.
  
 11.) A3, USP ANCHOR SCHEDULE, HTA20,
 NAILING CONFLICTS WITH CATALOG.
 ALLOWABLE LATERAL LOAD ON PLAN EXCEED
 PRODUCT LIMITATIONS.CHECK ALL
 CONNECTORS.
  
 12.)FLORIDA OR LOCAL PRODUCT
 APPROVALS
 REQUIRED FOR ALL PRODUCTS, USP ANCHOR
 SCHEDULE.SOME REFER TO NOAS.
 WWW.FLORIDABUILDING.ORG.
  
 13.) THERE ARE NOTES ON THE FLOOR PLAN
 FOR TEMPERED GLASS, BUT ANOTHER NOTE ON
 THE PLAN INDICATES THAT ALL WINDOWS
 WILL
 BE IMPACT.SOME PRODUCT APPROVALS
 SUBMITTED ARE FOR NONIMPACT PRODUCTS.
 ADDRESS.FOR PRODUCT APPROVALS
 COVERING
 SEVERAL PRODUCTS, INDICATE THE PRODUCT
 YOU ARE USING.
  
 14.)IMPACT PROTECTIONS REQUIRED
 FBC1606.1.4.IF GLAZING IS NOT IMPACT,
 PROVIDE PRODUCT APPROVALS AND HURRICANE
 SHUTTER INSTALLATION SCHEDULE OR A
 SEPARATE PERMIT FOR SHUTTERS WILL BE
 REQUIRED.CHANGE THE NOTES ON THE
 PLAN.
  
 15.)THE GARAGE JAMB DETAIL, A6,
 CONFLICTS WITH THE PRODUCT APPROVAL.
  
 16.)A6, WINDOW & SGD JAMB DETAIL,
 SPECIFY BUCK ATTACHMENT (LENGTH).
  
 17.)THE PLAN SPECIFIES CLAY BARREL
 TILE (A6), PRODUCT APPROVAL SUBMITTED
 IS
 FOR CONCRETE TILE.
  
 18.)THE TEST REPORT FOR THE ENTRY IS
 FOR GLAZED AND OPAQUE DOORS.
 FBC1005.4.5 REQUIRES A MEANS OF ESCAPE
 IN THE EVENT OF TEMPORARY INSTALLATION
 OF HURRICANE PROTECTION.IS THE FRONT
 DOOR GLAZED OR OPAQUE?
  
 19.)CASEMENT WINDOWS IN A 26 SIZE
 WERE
 SPECIFIED ON THE PLAN; PGT IMPACT
 PRODUCT APPROVALS SUBMITTED.THE
 WINDOWS ARE UNAVAILABLE IN THIS SIZE.
 ADDRESS.
  
 20.)FAC9B72, FLORIDA STATE OR LOCAL
 PRODUCT APPROVAL REQUIRED FOR ALL
 PRODUCTS.WWW.FLORIDABUILDING.ORG
  
  