2005-02-02 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| 1.)THE OWNER INFORMATION DOESN'T |
| MATCH |
| OUR RECORDS. |
| |
| 2.)THE NOC IS EXPIRED, MORE THAN 90 |
| DAYS WITHOUT COMMENCING WORK, |
| FS713.13(2). |
| |
| 3.)A3, THE NOTE REGARDING THE 10# LL |
| IS NOT IN COMPLIANCE WITH FBC TABLE |
| 1604.1.ATTICS WITH STORAGE ARE TO |
| HAVE |
| A 30# BCLL.ROOF FRAMING PLAN SHOWS |
| 10# |
| FOR STORAGE AREAS (TWO NOTES). |
| |
| 4.)THE FLOOR PLAN SHOWS THE ROOM |
| ADJACENT TO THE CABANA AS AN OFFICE, |
| ROOF FRAMING PLAN SHOWS IT AS A GUEST |
| ROOM.IS THIS AREA THE "GUEST HOUSE" |
| REFERRED TO ON THE PLAN?SLEEPING |
| ROOMS |
| ARE TO HAVE SMOKE DETECTORS IN |
| COMPLIANCE WITH FBC 905.2.2. |
| |
| 5.)THE TWO SETS OF PLANS SUBMITTED |
| HAVE DIFFERENT SIGNATURES AND DATES. |
| |
| 6.)SHEET T1, CONCRETE UNIT MASONRY, H |
| REFERS TO A CODE FOR HVHZ.CITY OF WPB |
| IS NOT IN THE HVHZ.PLEASE CORRECT |
| REFERENCES (ACI REFERENCES ARE |
| DIFFERENT |
| FOR HVHZ AS WELL). |
| |
| 7.SHEET T1, WIND LOADS (DESIGN |
| PARAMETERS), REFERS TO A STANDARD FOR |
| WOOD CONSTRUCTION WHICH I AM UNABLE TO |
| LOCATE IN THE FBC. |
| |
| 8.)A6, KNEE WALL ON GIRDER TRUSS, |
| REFERS TO HUGHES CONNECTORS.THEY HAVE |
| BEEN OUT OF BUSINESS FOR YEARS. |
| SPECIFY |
| ONLY AVAILABLE PRODUCTS. |
| |
| 9.)A3 (AT GARAGE) REFERS TO AHU |
| INSTALLATION DETAIL ON SHEET 9, BUT |
| THERE IS NO SHEET 9. |
| |
| 10.) ROUGH CARPENTRY NOTES (U), SHEET |
| T1, SPECIFIES 5/8" PLYWOOD WHICH |
| CONFLICTS WITH THE DETAILS. |
| |
| 11.) A3, USP ANCHOR SCHEDULE, HTA20, |
| NAILING CONFLICTS WITH CATALOG. |
| ALLOWABLE LATERAL LOAD ON PLAN EXCEED |
| PRODUCT LIMITATIONS.CHECK ALL |
| CONNECTORS. |
| |
| 12.)FLORIDA OR LOCAL PRODUCT |
| APPROVALS |
| REQUIRED FOR ALL PRODUCTS, USP ANCHOR |
| SCHEDULE.SOME REFER TO NOAS. |
| WWW.FLORIDABUILDING.ORG. |
| |
| 13.) THERE ARE NOTES ON THE FLOOR PLAN |
| FOR TEMPERED GLASS, BUT ANOTHER NOTE ON |
| THE PLAN INDICATES THAT ALL WINDOWS |
| WILL |
| BE IMPACT.SOME PRODUCT APPROVALS |
| SUBMITTED ARE FOR NONIMPACT PRODUCTS. |
| ADDRESS.FOR PRODUCT APPROVALS |
| COVERING |
| SEVERAL PRODUCTS, INDICATE THE PRODUCT |
| YOU ARE USING. |
| |
| 14.)IMPACT PROTECTIONS REQUIRED |
| FBC1606.1.4.IF GLAZING IS NOT IMPACT, |
| PROVIDE PRODUCT APPROVALS AND HURRICANE |
| SHUTTER INSTALLATION SCHEDULE OR A |
| SEPARATE PERMIT FOR SHUTTERS WILL BE |
| REQUIRED.CHANGE THE NOTES ON THE |
| PLAN. |
| |
| 15.)THE GARAGE JAMB DETAIL, A6, |
| CONFLICTS WITH THE PRODUCT APPROVAL. |
| |
| 16.)A6, WINDOW & SGD JAMB DETAIL, |
| SPECIFY BUCK ATTACHMENT (LENGTH). |
| |
| 17.)THE PLAN SPECIFIES CLAY BARREL |
| TILE (A6), PRODUCT APPROVAL SUBMITTED |
| IS |
| FOR CONCRETE TILE. |
| |
| 18.)THE TEST REPORT FOR THE ENTRY IS |
| FOR GLAZED AND OPAQUE DOORS. |
| FBC1005.4.5 REQUIRES A MEANS OF ESCAPE |
| IN THE EVENT OF TEMPORARY INSTALLATION |
| OF HURRICANE PROTECTION.IS THE FRONT |
| DOOR GLAZED OR OPAQUE? |
| |
| 19.)CASEMENT WINDOWS IN A 26 SIZE |
| WERE |
| SPECIFIED ON THE PLAN; PGT IMPACT |
| PRODUCT APPROVALS SUBMITTED.THE |
| WINDOWS ARE UNAVAILABLE IN THIS SIZE. |
| ADDRESS. |
| |
| 20.)FAC9B72, FLORIDA STATE OR LOCAL |
| PRODUCT APPROVAL REQUIRED FOR ALL |
| PRODUCTS.WWW.FLORIDABUILDING.ORG |
| |
| |