Plan Review Notes
Plan Review Notes For Permit 04121797
Permit Number 04121797
Review Stop E
Sequence Number 5
Notes
Date Text
2006-02-10 00:00:00***** UNSAT ****
  
 1)NOTE: PLEASE CORRELATE AHU HEAT LOADS
 ON PANEL SCHEDULE WIHT LOADS
 CALCULATIONS.
 PLEASE SEE TWO DIFFERENT LOADS ARE
 SHOWN.
 PLEASE SEE 65% OF 10KW IS NOT 7150VA,
 PLEASE ALSO SEE VA SHOWN FOR A/C AT 5KW?
 215.5
  
 2)NOTE: PLEASE CORRELATE FEEDERS FOR
 PANEL "C", RISER SHOWS #3, PANEL "A"
 SHOWS #4.
 310.16.240.40,310.15B6, 215.5
  
 3)NOTE: PLEASE CORRELATE FEEDERS FOR
 PANEL "B", RISER SHOWS #8'S AND SHOWS
 #12 ON PANEL SCHEDULE "A". PLEASE ALSO
 SEE NEITHER SETS OF FEEDERS ARE RATED
 FOR THE 80A BRKR FEEDING PANEL "B".
 240.4,310.15B6,310.16 ,215.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]