Plan Review Notes For Permit 04121797 |
Permit Number |
04121797 |
|
Review Stop |
E |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2006-02-10 00:00:00 | ***** UNSAT **** | | | | 1)NOTE: PLEASE CORRELATE AHU HEAT LOADS | | ON PANEL SCHEDULE WIHT LOADS | | CALCULATIONS. | | PLEASE SEE TWO DIFFERENT LOADS ARE | | SHOWN. | | PLEASE SEE 65% OF 10KW IS NOT 7150VA, | | PLEASE ALSO SEE VA SHOWN FOR A/C AT 5KW? | | 215.5 | | | | 2)NOTE: PLEASE CORRELATE FEEDERS FOR | | PANEL "C", RISER SHOWS #3, PANEL "A" | | SHOWS #4. | | 310.16.240.40,310.15B6, 215.5 | | | | 3)NOTE: PLEASE CORRELATE FEEDERS FOR | | PANEL "B", RISER SHOWS #8'S AND SHOWS | | #12 ON PANEL SCHEDULE "A". PLEASE ALSO | | SEE NEITHER SETS OF FEEDERS ARE RATED | | FOR THE 80A BRKR FEEDING PANEL "B". | | 240.4,310.15B6,310.16 ,215.5 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|