2006-01-23 00:00:00 | ********** UNSAT ********** |
| |
| 1)NOTE: PLEASE SEE NOTE #10 ON E-2 WHICH |
| INDICATES 250.95, WHICH IS FROM THE 1996 |
| NEC. THIS HAS BEEN REDLINED ON PREVIOUS |
| PLANS, HOWEVER PLEASE CORRECT AT THIS |
| TIME. |
| |
| 2)NOTE: PLEASE SEE MIN VA SHALL BE 1.5KW |
| FOR SMALL APPL, WAS/LAUNDRY CIRCUITS. |
| 220.12 |
| SHOWS 1.0 |
| |
| 3)NOTE: PLEASE VERIFY ALL LOADS IN PANEL |
| "C" AS BOTH CU'S INDICATE LOAD TOGETHER |
| AS 2.8VA. THIS IS NOT POSSIBLE AS UNITS |
| ARE TOO LARGE FOR THIS LOW OF A LOAD. |
| PLEASE ALSO SEE LOAD FOR SPRINKLER TIME |
| CLOCK, IS THIS A PUMP OR ONLY TC.VERIFY |
| LOAD.? |
| PLEASE SEE LOADS ARE NOT COMPLETE IN |
| THIS PANEL "C". |
| |
| |
| 4)NOTE: PLEASE SEE PANEL "A" SHOWS KW |
| RATING AT 10KW , HOWEVER LOAD CALCS |
| INDICATE BOTH OF THESE AT 7.15 KW? |
| PLEASE EXPLAIN OR SHOW. IF DE-RATING IS |
| BEING CALCULATED , THEN PLEASE SHOW. |
| |
| 5)NOTE: PLEASE SEE KITCHEN ISLAND WHERE |
| THE GFI LABEL SEEMS TO BE LOCATED OFF |
| THE RECEPT IN WHICH IT IS SUPPOSE TO |
| LABEL. (MISPRINT). PLEASE SEE ONE SET IS |
| REDLINED FOR THIS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |