| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| 1}THE PLAN SHOWS A METER/MAIN AND THE |
| RISER SHOWS A PANEL AND METER SEPERATE, |
| PLEASE CORRELATE. |
| |
| NOTE: USING FIVE 2-POLE BREAKERS AS |
| "MAINS" IN A TWELVE SPACE PANEL LEAVES |
| ROOM FOR TWO SINGLE POLE BREAKERS, NOT |
| MEETING THE INTENT OF THE SIX MEANS OF |
| DISCONNECT IN ARTICLE 230.70, 71 OR THE |
| EXCEPTIONS OUTLINED IN 230.40. |
| |
| 2} THE DEMAND CALCULATION SHOWS A/C #1 & |
| #2 AS 5000 WATTS, PANELSCHEDULE SHOWS |
| 11000, AND THE LOADS ARE SHOWN AS 7150 W |
| AFTER DEMAND . PLEASE CORRELATE. |
| |
| 3} NOTE: THE LOAD CALCULATION AFTER |
| DEMAND IS 199 AMPS ON A 200 AMP SERVICE |
| LEAVING NO ROOM FOR FUTURE ADDITIONAL |
| LOADS. WHILE THIS SERVICE DOES MEET THE |
| MINIMUM CRITERIA A LARGER SERVICE IS |
| RECOMMENDED. |
| |
| 4} THE TERM "ARCHITECTS" IN THE TITLE |
| BLOCK INDICATES A FIRM OR BUSINESS AND |
| THEREFORE REQUIRES A CERTIFICATE OF |
| AUTHORIZATION NUMBER ALSO ON THE TITLE |
| BLOCK PER 61G1-16.004(2) FAC. |
| |