Plan Review Notes
Plan Review Notes For Permit 04121739
Permit Number 04121739
Review Stop B
Sequence Number 1
Notes
Date Text
2005-01-13 00:00:00DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) PLAN SHEETS SD1 AND SD2 DO NOT HAVE
 THE ORIGINAL WET SIGNATURE OF THE
 ENGINEER AS REQUIRED BY FAC
 61G15-23.002.
  
 3) ON SHEET RF-1 THE UPLIFT VALUE FOR
 THE USC 53 CONNECTOR INCLUDES THE ONE
 THIRD INCREASE IN THE STEEL
 CALCULATIONS
 WHICH IS NOT ALLOWED BY FBC 1609.4.3.
 THE MAXIMUM UPLIFT IS 11,150# PER
 MANUFACTURER'S CATALOG.
  
 4) SUBMIT TWO COPIES OF PRODUCT
 APPROVALS, KEY PLANS AND INSTALLATION
 SCHEDULES FOR THE STORM PANELS OR APPLY
 UNDER A SEPARATE PERMIT.
  
 5) THE PRODUCT APPROVALS FOR THE GARAGE
 DOORS HAVE THE WRONG EVALUATION
 REPORTS.
 SUBMIT THE PROPER EVALUATION/TEST
 REPORT
 AND INSTALLATION INSTRUCTIONS THAT ARE
 POSTED ON THE STATE PRODUCT APPROVAL
 WEBSITE.
  
 6) THE MIAMI-DADE NOA FOR THERMA-TRU
 CORPORATION ATTACHED TO THE STATE
 PRODUCT APPROVAL FOR BENCHMARK APPEAR
 TO
 BE TWO DIFFERENT PRODUCTS. SUBMIT
 DOCUMENTATION THAT THESE ARE THEY SAME
 COMPANY AND THE SAME PRODUCT.
  
 7) SUBMIT STATE/LOCAL PRODUCT APPROVAL
 FOR STRUCTURAL WINDOW MULLIONS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714