Date |
Text |
2005-01-13 00:00:00 | DENIED |
| |
| 1)A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) PLAN SHEETS SD1 AND SD2 DO NOT HAVE |
| THE ORIGINAL WET SIGNATURE OF THE |
| ENGINEER AS REQUIRED BY FAC |
| 61G15-23.002. |
| |
| 3) ON SHEET RF-1 THE UPLIFT VALUE FOR |
| THE USC 53 CONNECTOR INCLUDES THE ONE |
| THIRD INCREASE IN THE STEEL |
| CALCULATIONS |
| WHICH IS NOT ALLOWED BY FBC 1609.4.3. |
| THE MAXIMUM UPLIFT IS 11,150# PER |
| MANUFACTURER'S CATALOG. |
| |
| 4) SUBMIT TWO COPIES OF PRODUCT |
| APPROVALS, KEY PLANS AND INSTALLATION |
| SCHEDULES FOR THE STORM PANELS OR APPLY |
| UNDER A SEPARATE PERMIT. |
| |
| 5) THE PRODUCT APPROVALS FOR THE GARAGE |
| DOORS HAVE THE WRONG EVALUATION |
| REPORTS. |
| SUBMIT THE PROPER EVALUATION/TEST |
| REPORT |
| AND INSTALLATION INSTRUCTIONS THAT ARE |
| POSTED ON THE STATE PRODUCT APPROVAL |
| WEBSITE. |
| |
| 6) THE MIAMI-DADE NOA FOR THERMA-TRU |
| CORPORATION ATTACHED TO THE STATE |
| PRODUCT APPROVAL FOR BENCHMARK APPEAR |
| TO |
| BE TWO DIFFERENT PRODUCTS. SUBMIT |
| DOCUMENTATION THAT THESE ARE THEY SAME |
| COMPANY AND THE SAME PRODUCT. |
| |
| 7) SUBMIT STATE/LOCAL PRODUCT APPROVAL |
| FOR STRUCTURAL WINDOW MULLIONS. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |