Plan Review Notes
Plan Review Notes For Permit 04121358
Permit Number 04121358
Review Stop E
Sequence Number 2
Notes
Date Text
2005-03-02 00:00:00****** UNSAT 2ND REVIEW ******
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
 1)NOTE: NOTE #1 OK.
  
 2)NOTE: NOTE #2 NO
  
 3)NOTE: NOTE #3 NO.
  
 4)NOTE: NOTE #4 NO.
  
 NEW NOTES.
  
 1)NOTE: PLEASE SEE SERVICE IS NOW SHOWN
 AS 300A'S, PLEASE SEE PREVIOUS NOTES AND
 VERIFY AND SHOW EXSITING SEC'S.
 310.16,240.4
  
 2)NOTE: PLEASE SEE PANEL "B" IS SHOWN
 "OUTSIDE" OF UNIT. PLEASE SEE DOORS.
 PANEL "B" INDICATES PANEL IN LAUNDRY RM.
  
 3)NOTE: PLEASE CORRELATE MECHANICAL
 PLANS WITH ELECTRICAL PLANS FOR AHU KW
 LOADS. ONE FOR UNIT IS SHOWN AS 7KW AND
 ELECTRICAL SHOWS 4.5KW.
  
 4)NOTE: PLEASE SEE 220.31B, AHU, HEAT IS
 FIGURED AT 100% AND MAY NOT TAKE A
 DERATING OF 65% ON EXISTING
 SERVICES/DWELLINGS.
  
 5)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) ATTACHED. THIS IS ONLY A
 NOTICE THAT IS GIVEN AT THIS TIME.
  
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO COMPLETE SETS FOR
 REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  