Plan Review Notes
Plan Review Notes For Permit 04121358
Permit Number 04121358
Review Stop E
Sequence Number 1
Notes
Date Text
2004-12-28 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE SEE SD'S ARE INDICATED AS
 WIRED TO LT CIRCUIT IN LIV RM ETC.
 THIS IS FINE HOWEVER, PLEASE BE AWARE
 UNDER THE 2002 NEC 210.12, "ALL OUTLETS"
 IN BEDRMS ARE REQUIRED TO HAVE ARC FAULT
 PROTECTION. THIS WOULD INCLUDE THESE
 ADDITIONAL CIRCUITS UNLESS SD'S ARE
 PLACED ON WITH BEDRM CIRCUIT(S).
  
 2)NOTE: PLEASE VERIFY AND/OR NOTE SIZE
 OF EXISTING SEC'S FOR 250A SERVICE AS
 SHOWN.
 PLEASE SEE MIN SEC'S PER 310.16, 240.4B
  
 3)NOTE: PLEASE VERIFY EXISTING GROUNDING
 ELECTRODE SYSTEM TO MEET 250.50 WITH THE
 EXCEPTION OF EXISTING FOOTER STEEL.
  
 4)NOTE: PLEASE SEE MISSING RECEPT ON 2'
 OF WALL SPACE IN BEDRM #2 SECOND FLR.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  