2005-02-07 00:00:00 | ********* UNSAT 2ND REVIEW ********** |
| |
| PLEASE SEE SOME COMMENTS FROM PREVIOUS |
| REVIEW STILL NEED TO BE ADDRESSED. |
| |
| |
| 1)NOTE: PLEASE SEE PLANS WHICH ARE |
| SIGNED, DATED AND SEALED BY THE ENGINEER |
| MUST CONTAIN A TITLE BLOCK FOR THE |
| ENGINEER OF RECORD CONTAINING ALL |
| INFORMATION AS REQUIRED UNDER FAC |
| 61G15-23.002. |
| |
| |
| 2)NOTE: PLEASE CORRELATE LOAD |
| CALCULATIONS, SUB-PANEL IS SHOWN W/ 25KW |
| LOAD AND MAIN PANEL INDICATES 10KW? |
| PLEASE SEE 220.31 FOR LOAD |
| CALCULATIONS. |
| PLEASE SEE 220.3B4, THIS IS A TOTAL # OF |
| FIXTURES X THE WATTAGE PER FIXTURE ADDED |
| TO LIGHTING LOAD CALCS. |
| |
| |
| NEW COMMENTS DUE TO CHANGE IN RISER |
| DIAGRAM AND ADDED PANEL SCHEDULE. |
| |
| 1)NOTE: PLEASE SEE REQUIRED FOOTER STEEL |
| HAS NOW BEEN REMOVED FROM RISER |
| DIAGRAM? |
| PLEASE SEE 250.50. |
| |
| 2)NOTE: PLEASE SEE SMALL APPL CIRCUIT IS |
| SHOWN W/ 3KW LOAD ON A 20A CIRCUIT. |
| PLEASE SEE MAX KW FOR A 20A CIRCUIT IS |
| 1950W'S. PLEASE ADJUST. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| PLEASE REMOVE ANY OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| |
| |