Plan Review Notes
Plan Review Notes For Permit 04121181
Permit Number 04121181
Review Stop E
Sequence Number 1
Notes
Date Text
2004-12-30 00:00:00*************** UNSAT *************
  
 1)NOTE: PLEASE SEE PLANS WHICH ARE
 SIGNED AND SEALED BY THE ENGINEER ARE
 REQUIRED TO HAVE A TITLE BLOCK WITH ALL
 INFORMATION AS SET-FORTH IN FAC
 61G15-23.002. PLEASE SEE ELECTRICAL
 PLANS DO NOT CONTAIN ANY TITLE BLOCK FOR
 ENG.
 PLEASE SEE ALL PLANS ARE REQUIRED TO
 HAVE THE PRINTED NAME AND SIAGNATURE OF
 PERSON RESPONSIBLE FOR PLANS/DESIGN. PER
 FBC 104.2.1 THIS IS REQUIRED ON ALL
 PLANS AND FOR ALL TRADES WHEATHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 2)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 PLEASE SEE MOST HAVE BEEN REDLINED ON
 PLANS FOR LOCATIONS REQUIRED.
  
 3)NOTE: PLEASE CORRELATE PLANS WITH
 PANEL SCHEDULE AND LOAD CALCULATIONS FOR
 WATER HEATER, OVEN/RANGE AND DRYER.
 PLANS SHOW AS GAS AND ELECTRICAL WITH
 LOADS ACCORD.
 PLEASE SEE WATER HOWEVER SHOWS A LOAD OF
 4500W ON A 20A CIRCUIT.
 PLEASE SEE 422.13, REQUIRES MIN RATING
 OF 125%.
  
 4)NOTE: PLEASE VERIFY OCP FOR AHU #2,
 THIS SHOWS 60A OCP FOR 7.5KW UNIT.
 424.3B REQUIRES A MIN 125% . MAX MAY BE
 150% FOR OCP.
  
 5 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 6 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 7)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS
 ON PLANS.
  
 8)NOTE: PLEASE INDICATE PANEL AS MCB.
 225.31,240.4B,ETC.
  
 PLEASE REMOVE ANY OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE ONLY.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved