Date |
Text |
2004-12-30 00:00:00 | *************** UNSAT ************* |
| |
| 1)NOTE: PLEASE SEE PLANS WHICH ARE |
| SIGNED AND SEALED BY THE ENGINEER ARE |
| REQUIRED TO HAVE A TITLE BLOCK WITH ALL |
| INFORMATION AS SET-FORTH IN FAC |
| 61G15-23.002. PLEASE SEE ELECTRICAL |
| PLANS DO NOT CONTAIN ANY TITLE BLOCK FOR |
| ENG. |
| PLEASE SEE ALL PLANS ARE REQUIRED TO |
| HAVE THE PRINTED NAME AND SIAGNATURE OF |
| PERSON RESPONSIBLE FOR PLANS/DESIGN. PER |
| FBC 104.2.1 THIS IS REQUIRED ON ALL |
| PLANS AND FOR ALL TRADES WHEATHER OR NOT |
| COMMENT IS MADE BY OTHER REVIEWER(S). |
| |
| 2)NOTE: SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| UNIT. |
| IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| TO FLOORS ABOVE AND IN THE VICINITY OF |
| BEDROOMS. |
| PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| A MIN OF 3' FROM BATHROOM DOORS AND |
| KITCHENS. |
| ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| PLEASE SEE MOST HAVE BEEN REDLINED ON |
| PLANS FOR LOCATIONS REQUIRED. |
| |
| 3)NOTE: PLEASE CORRELATE PLANS WITH |
| PANEL SCHEDULE AND LOAD CALCULATIONS FOR |
| WATER HEATER, OVEN/RANGE AND DRYER. |
| PLANS SHOW AS GAS AND ELECTRICAL WITH |
| LOADS ACCORD. |
| PLEASE SEE WATER HOWEVER SHOWS A LOAD OF |
| 4500W ON A 20A CIRCUIT. |
| PLEASE SEE 422.13, REQUIRES MIN RATING |
| OF 125%. |
| |
| 4)NOTE: PLEASE VERIFY OCP FOR AHU #2, |
| THIS SHOWS 60A OCP FOR 7.5KW UNIT. |
| 424.3B REQUIRES A MIN 125% . MAX MAY BE |
| 150% FOR OCP. |
| |
| 5 )NOTE: PLEASE SEE 220.3B4. |
| PLEASE SHOW ALL RECESSED LTS BASED ON |
| MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| BE FIGURED IN W/ 3W/PER SQ FT. |
| PLEASE PROVIDE FIXTURE INFORMATION ON |
| LEGEND. |
| |
| 6 )NOTE: PLEASE LIST THE REQ'D ARC |
| FAULT PROTECTED CURCUIT(S) ON PANEL |
| SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| IN BEDROOMS ARE TO BE PROTECTED , |
| INCLUDING, LTS, RECEPTS, SD'S ETC. |
| |
| 7)NOTE: PLEASE PROVIDE ROOM DESIGNATIONS |
| ON PLANS. |
| |
| 8)NOTE: PLEASE INDICATE PANEL AS MCB. |
| 225.31,240.4B,ETC. |
| |
| PLEASE REMOVE ANY OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| ONE SET OF OLD SHEETS SHOULD BE |
| SUBMITTED FOR REFERENCE ONLY. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |