Plan Review Notes
Plan Review Notes For Permit 04121181
Permit Number 04121181
Review Stop B
Sequence Number 1
Notes
Date Text
2005-01-12 00:00:00DENIED
  
 1)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SUBMIT A SURVEY INDICATING THE
 LOCATION OF THE STRUCTURE ON THE LOT.
  
 4) THE LOCATIONS OF SEVERAL OF THE
 FILLED CELLS ARE MISSING FROM THE
 FOUNDATION PLAN ON A1.
  
 5) SPECIFY THE EMBED DEPTH OF THE 1/2"
 DIA. BOLTS ON THE O.H. GARAGE DOOR BUCK
 DETAIL ON A 2.
  
 6) SPECIFY THE LOCATIONS OF THE DRAFT
 STOPS DIVIDING THE FLOOR/CEILING
 ASSEMBLY INTO AREAS OF 500 SQFT AS
 REQUIRED BY FBC 2305.2.2.
  
 7) SUBMIT MANUFACTURERS SPECIFICATIONS
 AND INSTALLATION INSTRUCTIONS FOR THE
 FOAM INSULATION THAT WILL BE USED IN
 CONJUNCTION WITH THE UNVENTED ATTIC.
 ALSO SEE ATTACHMENT.
  
 8) THE MEAN ROOF HEIGHT OF LESS THAN 20'
 LISTED ON SHEETS A4 AND A6 IS INCORRECT.
 THE MRH (DISTANCE FROM GRADE TO AVERAGE
 HEIGHT OF THE ROOF) IS JUST OVER 26'.
 PLEASE CORRECT.
  
 9) REVISE ROOF SHEATHING NAILING NOTES
 ON A4. THE OUTSIDE CORNERS OF HIP ROOFS
 ARE ZONE 3. SHEATING IN ZONE 3 IS
 REQUIRED TO BE NAILED AT 4'OC AT EDGES
 AND 6'OC INTERMEDIATE WITH 8D RING-SHANK
 NAILS PER CITY OF WPB AMENDMENTS TO FBC
 TABLE 2306.1.
  
 10) REVISE THE ROOF SHEATHING FASTENING
 NOTES AT THE ONE AND TWO STORY WALL
 SECTIONS ON A5.
  
 11) PLEASE CORRECT THE NUMBER OF
 FASTENERS SPECIFIED FOR TRUSS CONNECTOR
 #4 IN THE SCHEDULE ON A4. THE SIMPSON
 CATALOG SPECIFIES (15) 10D X 1-1/2"
 NAILS FOR THE HETAL 20.
  
 12) PROVIDE A FASTENING DETAIL FOR THE
 LEDGER CARRYING THE ROOF TRUSSES AT THE
 CHIMNEY.
  
 13) SUBMIT A LETTER FROM THE
 MANUFACTURER OF THE FIREPLACE AND
 CHIMNEY SPECIFYING THAT THE CHIMNET
 TERMINATION CAP CAN BE ENCLOSED AS SHOWN
 ON THE PLANS. ADDRESS THE FIRE HAZARD
 AND THE ABILITY OF THE UNIT TO DRAFT
 PROPERLY.
  
 14) SUBMIT A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS. SPECIFY
 WHICH OPENINGS WILL BE SHUTTERED.
 SPECIFY THE MOUNT TYPE, FASTENER TYPE
 AND SPACING.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714