2005-01-12 00:00:00 | DENIED |
| |
| 1)IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 2)A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 3) SUBMIT A SURVEY INDICATING THE |
| LOCATION OF THE STRUCTURE ON THE LOT. |
| |
| 4) THE LOCATIONS OF SEVERAL OF THE |
| FILLED CELLS ARE MISSING FROM THE |
| FOUNDATION PLAN ON A1. |
| |
| 5) SPECIFY THE EMBED DEPTH OF THE 1/2" |
| DIA. BOLTS ON THE O.H. GARAGE DOOR BUCK |
| DETAIL ON A 2. |
| |
| 6) SPECIFY THE LOCATIONS OF THE DRAFT |
| STOPS DIVIDING THE FLOOR/CEILING |
| ASSEMBLY INTO AREAS OF 500 SQFT AS |
| REQUIRED BY FBC 2305.2.2. |
| |
| 7) SUBMIT MANUFACTURERS SPECIFICATIONS |
| AND INSTALLATION INSTRUCTIONS FOR THE |
| FOAM INSULATION THAT WILL BE USED IN |
| CONJUNCTION WITH THE UNVENTED ATTIC. |
| ALSO SEE ATTACHMENT. |
| |
| 8) THE MEAN ROOF HEIGHT OF LESS THAN 20' |
| LISTED ON SHEETS A4 AND A6 IS INCORRECT. |
| THE MRH (DISTANCE FROM GRADE TO AVERAGE |
| HEIGHT OF THE ROOF) IS JUST OVER 26'. |
| PLEASE CORRECT. |
| |
| 9) REVISE ROOF SHEATHING NAILING NOTES |
| ON A4. THE OUTSIDE CORNERS OF HIP ROOFS |
| ARE ZONE 3. SHEATING IN ZONE 3 IS |
| REQUIRED TO BE NAILED AT 4'OC AT EDGES |
| AND 6'OC INTERMEDIATE WITH 8D RING-SHANK |
| NAILS PER CITY OF WPB AMENDMENTS TO FBC |
| TABLE 2306.1. |
| |
| 10) REVISE THE ROOF SHEATHING FASTENING |
| NOTES AT THE ONE AND TWO STORY WALL |
| SECTIONS ON A5. |
| |
| 11) PLEASE CORRECT THE NUMBER OF |
| FASTENERS SPECIFIED FOR TRUSS CONNECTOR |
| #4 IN THE SCHEDULE ON A4. THE SIMPSON |
| CATALOG SPECIFIES (15) 10D X 1-1/2" |
| NAILS FOR THE HETAL 20. |
| |
| 12) PROVIDE A FASTENING DETAIL FOR THE |
| LEDGER CARRYING THE ROOF TRUSSES AT THE |
| CHIMNEY. |
| |
| 13) SUBMIT A LETTER FROM THE |
| MANUFACTURER OF THE FIREPLACE AND |
| CHIMNEY SPECIFYING THAT THE CHIMNET |
| TERMINATION CAP CAN BE ENCLOSED AS SHOWN |
| ON THE PLANS. ADDRESS THE FIRE HAZARD |
| AND THE ABILITY OF THE UNIT TO DRAFT |
| PROPERLY. |
| |
| 14) SUBMIT A KEY PLAN AND INSTALLATION |
| SCHEDULE FOR THE STORM PANELS. SPECIFY |
| WHICH OPENINGS WILL BE SHUTTERED. |
| SPECIFY THE MOUNT TYPE, FASTENER TYPE |
| AND SPACING. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |