Date |
Text |
2004-12-30 00:00:00 | ************ UNSAT *************** | | | | 1)NOTE: PLEASE SEE FBC 104.2.1, WHICH | | REQUIRES THE PRINTED NAME AND SIGNATURE | | OF PERSON RESPONSIBLE FOR PLANS AND | | DESIGN FOR SCOPE OF WORK. | | | | 2)NOTE: PLEASE PROVIDE A RISER DIAGRAM | | SHOWING THE CHANGE OUT OF 5-GANG | | METERCAN. PLEASE VERIFY IF MAINS ARE | | GROUPED AS REQUIRED PER 230.70,230.72, | | PLEASE ALSO VERIFY SEC'S PER | | 310.16,240.4 AND GROUNDING PER 250.50 | | | | | | 3)NOTE: PLEASE SEE PANEL "A" IS NOTED AS | | BEING EXSITING WITH #2, AND LOAD AT | | 109A'S, HOWEVER PLEASE INDICATE SIZE OF | | MCB. | | 215.5 | | | | 4)NOTE: PLEASE SEE 220.16B, MIN KW | | RATING FOR WASHER/LAUNDRY LOAD IS | | 1500VA. PLEAS ADJUST LOAD CALCS. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|