Plan Review Notes
Plan Review Notes For Permit 04121138
Permit Number 04121138
Review Stop E
Sequence Number 1
Notes
Date Text
2004-12-28 00:00:00************ UNSAT ***********
  
 1)NOTE: PLEASE SEE WIRING DIAGRAM
 INDICATES A NEW PANEL.
 PLEASE INCLUDE FEED TO NEW PANEL, OCP,
 AWG, CONDUIT ETC.
 PLEASE ALSO INCLUDE PANEL SCHEDULE FOR
 NEW PANEL WITH CIRCUITS FOR NEW
 EQUIPMENT.215.5
  
 2)NOTE: PLEASE BE SURE RAISED SEAL IS
 CLEAR AND VISABLE WITH ALL INFORMATION
 ON SEAL. FS 471.025
  
 3)NOTE: PLEASE INCLUDE MANUFACTURE SPECS
 FOR HEAT PUMP SHOWING LISTING FROM A
 NRTL>
  
 4)NOTE: PLEASE INCLUDE LOAD CALCULATIONS
 FOR EXSITING SERVICE WITH NEW ADDED
 LOADS.
 PLEASE SEE ALL CONTINUOUS LOADS ARE TO
 BE SHOWN AT 125% (PUMP, HEAT PUMP).
 220
 IF LOAD CALCS ARE DONE BY THE ELECTRICAL
 CONTRACTOR, PLEASE BE SURE THE PRINTED
 NAME AND SIGNATURE IS ON SEPARATE
 SHEETS.
 FBC 104.2.1
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]