2005-01-04 00:00:00FIRE REVIEW FAILED
  
 1) NEW FIRE ALARM SYSTEMS SHALL BE UL
 LISTED FOR CENTRAL STATION SERVICE.
  
 2) ALL NEW FIRE ALARM SYSTEMS THAT
 SUPERVISE FIRE SPRINKLER SYSTEMS SHALL
 BE UL CERTIFICATED AND HAVE DOCUMENTS
 ATTESTING TO THIS CERTIFICATION PRIOR TO
 FINAL APPROVAL OF THE FIRE ALARM
 SYSTEM.
  
 3) FIRE ALARM CIRCUITS SHALL BE CLASS A,
 STYLE D IN THE CITY OF WEST PALM BEACH.
  