Plan Review Notes
Plan Review Notes For Permit 04121034
Permit Number 04121034
Review Stop E
Sequence Number 1
Notes
Date Text
2004-12-28 00:00:00**************** UNSAT *************
  
 1)NOTE: PLEASE SEE FAC 61G1-16.004 AND
 FAC 61G15-23.002 FOR MISSING LICENSE
 INFORMATION FOR ARCHITECTS AND
 ENGINEERINGFIRM PER FS 481.219,
 471.023.
 THIS INFORMATION IS REQUIRED FOR ALL
 TRADES AND FOR ALL SHEETS WHEATHER OR
 NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 2)NOTE: PLANS WHICH CONTAIN THE TITLE
 BLOCK FOR ENGINEER RESPONSIBLE FOR
 PLANS/DESIGN, MUST SIGN, DATE AND SEAL
 PLANS. FS 471.025
  
 3)NOTE: PLEASE SEE 220.31B FOR LOAD
 CALCUALTIONS.
  
 4)NOTE: PLEASE INDICATE EXISTING MCB
 SIZE.
  
  
 **PLEASE NOTE***
 PLANS MENTIONS KNOB AND TUBE WIRING
 PRESENT.
 UPON SERVICE CHANGE, IF KNOB AND TUBE
 IS
 STILL PRESENT THEN, THE CONNECTION OF
 THESE CIRCUITS WILL NOT BE PERMITTED.
 RE-WIRE MUST BE PERMITTED AND COMPLETE
 BEFORE CALLING IN FINALS FOR PERMITS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  