2004-12-28 00:00:00**************** UNSAT *************
  
 1)NOTE: PLEASE SEE FAC 61G1-16.004 AND
 FAC 61G15-23.002 FOR MISSING LICENSE
 INFORMATION FOR ARCHITECTS AND
 ENGINEERINGFIRM PER FS 481.219,
 471.023.
 THIS INFORMATION IS REQUIRED FOR ALL
 TRADES AND FOR ALL SHEETS WHEATHER OR
 NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 2)NOTE: PLANS WHICH CONTAIN THE TITLE
 BLOCK FOR ENGINEER RESPONSIBLE FOR
 PLANS/DESIGN, MUST SIGN, DATE AND SEAL
 PLANS. FS 471.025
  
 3)NOTE: PLEASE SEE 220.31B FOR LOAD
 CALCUALTIONS.
  
 4)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN HOUSE TO
 APT PANEL. PLEASE ALSO INCLUDE GROUND
 RODS AND CWP AT DETACHED BLDG. PER
 250.32
  
 5)NOTE: PLEASE SEE 310.15B6 FOR MIN
 SEC'S 240.4B.
 PLEASE ALSO ADJUST GROUNDING ELECTRODE
 CONDUCTOR TO A MIN OF #2. PER 250.66
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  