2005-01-06 00:00:00 | BUILDING PLAN REVIEW FAILED: |
| |
| |
| |
| 1. PRODUCT APPROVALS SUBMITTED |
| WITH PERMIT APPLICATION AFTER OCTOBER 1, |
| 2003 ARE REQUIRED TO COMPLY WITH THE |
| FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| INFORMATION PLEASE SEE THE STATE WEBSITE |
| AT WWW.FLORIDABUILDING.ORG. PRODUCTS |
| WITH STATEWIDE APPROVAL ARE REQUIRED TO |
| BE SUBMITTED WITH A COVER SHEET THAT |
| LISTS THE PRODUCT IDENTITY NUMBER FROM |
| THE STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| SUBMIT THE FLORIDA PRODUCT APPROVALS FOR |
| THE WINDOWS, DOORS & STORM PANELS. |
| |
| 2. SUBMIT THE DADE COUNTY PRODUCT |
| APPROVALS FOR THE WINDOWS. |
| |
| 3. THE WINDOW DRAWINGS BY DONALD W. |
| SHACKELFORD P.E. SHOWS WINDOW #4 TO BE |
| 36" X 26".THW WINDOW SCHEDULE ON THE |
| PLANS SHOWS IT TO BE 37" X 26" |
| |
| 4. SEE ELECTRICAL COMMENTS REGARDING THE |
| SEAL & SIGNATURE REQUIREMENTS. |
| |
| ANY QUESTIONS PLEASE CALL: |
| LEA SMITH, BUILDING PLANS EXAMINER |
| 805-6713 |