2005-01-07 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 04120940 |
| ADD: 1450 CENTREPARK BLVD# 340 |
| CONT:BURKHARDT |
| TEL: (561)718-2602 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 1)PROVIDE NOC RECORDED WITH THE CLERK OF |
| COURT BEFORE A PERMIT CAN BE ISSUED. |
| |
| 2) 704.2.1.4 CORRIDOR PARTITIONS, SMOKE |
| STOP PARTITIONS, HORIZONTAL EXIT PART- |
| ITIONS, EXIT ENCLOSURES, AND FIRE |
| RATED WALLS REQUIRED TO HAVE PROTECTED |
| OPENINGS SHALL BE EFFECTIVELY AND |
| PERMANETLY IDENTIFIED WITH SIGNS OR |
| STENCILING IN A MANNER ACCEPTABLE TO THE |
| AUTHORITY HAVING JURISDICTION. SUCH IDEN |
| TIFICATION SHALL BE ABOVE ANY DECORATIVE |
| CEILING CEILING AND IN CONCEALED SPACES. |
| SUGGESTED WORDING" FIRE & SMOKE BARRIER |
| PROTECT ALL OPENINGS". |
| |
| 3) A-1 INDICATES VARIOUS DOORWAY NOT |
| MEETING THE HANDICAPPED CLEARENCE |
| REQUIREMENTS FOR A FRONT OR SIDE |
| APPROACH.11-4.13.6 MANEUVERING |
| CLEARENCES AT DOORS. MINIMUM MANEUVERING |
| CLEARENCES AT DOORS THAT ARE NOT |
| AUTOMATIC OR POWER-ASSISTED SHALL BE AS |
| SHOWN IN FIG. 25. THE FLOOR OR GROUND |
| AREA WITH IN THE REQUIRED CLEARENCES |
| SHALL BE CLEAR & LEVEL. |
| |
| BUILDING PLAN REVIEW |