2006-08-09 00:00:00PLAN RESTAMP DENIED
  
 PLANS SUBMITTED ARE NOT EXACT MATCH OF
 APPROVED FILE SET.
  
 1) SHEET SP-1 DOES NOT HAVE PRIVACY
 WALLS AND WALL AND GATE ON RIGHT SIDE
 HAS BEEN MOVED. FILE PLANS ONLY HAVE
 REVISIONS 1 AND 2.
  
 2) SHEET A-1 DOES NOT REFLECT THE
 REDLINE CHANGES MADE BY J. BRASSEUR TO
 GAME ROOM ENERGY CALC. NOTES. CHANGED
 CEILING INSULATION TO R-20 AND INDICATED
 CEILING FANS.
  
 3) SHEET S-5 HAS REDLINE CHANGE BY
 D.O.R. TO R-20 AT GARAGE WALL SECTION.
  
 4)SHEET S-8 HAS REDLINE CHANGE BY D.O.R.
 TO R-20 FOR ICYENE R-VALUE AT GARAGE
 PARAPET DETAIL.
  
 5) CONTRACTOR NEEDS TO SUBMIT REVISED
 SHEET A-3 SPECIFYING THE CHANGE FROM
 SLOPED ROOF TO FLAT AT THE GARAGE. THIS
 SHEET WAS NOT SUBMITTED WHEN GARAGE ROOF
 WAS CHANGED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  