2006-08-20 00:00:00********* UNSAT ********
  
 1) NOTE: PLEASE CORRELATE PANELS, RISER
 AND PLANS.
 PLEASE SEE PANEL WHICH IS SHOWN ON RISER
 AS A 200 FEED-THRU PANEL, YET NO PANEL
 SCHEDULE ETC WAS SUBMITTED.
 PLEASE ALSO SEE THIS IS NOT SHOWN ON
 PLANS.
 THIS SHOUDL AHVE A MCB.
 225.31, FBC 106.1.2
  
 2) NOTE: PLEASE CORRELATE SIZES OF
 PANELS ON PANEL SCHEDULES AND WHAT IS
 BEING SHOWN ON RISER.
  
 3) NOTE: PLEASE CORRELATE FEEDERS ON
 RISER AND PANEL SCHEDULES. PLEASE SEE
 3/0, AND #1'S ETC FOR 100A BRKR FEED TO
 THE SUB PANEL.
  
  
 4) NOTE: PLEASE SEE PANEL SCHEDULE
 CIRCUTING DOES NOT SEEM TO START UNTIL
 ABOUT 1/3 THE WAY DOWN THE PANEL.
 PLEASE VERIFY THIS AS THIS IS NOT THE
 WAY IT IS ON THE JOBSITE.
  
  
 ** PLEASE KNOW, MANY ITEMS ON THE
 JOBSITE DOES NOT MATCH WITH PLANS.
 PLEASE KNOW, A PLAN REVIEW WAS DONE WITH
 THE ELECTRICAL INPECTOR AND CONTRACTOR
 ON THE PHONE AND MANY ITEMS SHOWN ON
 THESE PLANS DO NOT MATCH WITH WHAT IS
 INSTALLED IN FIELD. PLEASE GET WITH THE
 CONTRACTOR AND VERIFY ALL.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  