2006-08-20 00:00:00 | ********* UNSAT ******** |
| |
| 1) NOTE: PLEASE CORRELATE PANELS, RISER |
| AND PLANS. |
| PLEASE SEE PANEL WHICH IS SHOWN ON RISER |
| AS A 200 FEED-THRU PANEL, YET NO PANEL |
| SCHEDULE ETC WAS SUBMITTED. |
| PLEASE ALSO SEE THIS IS NOT SHOWN ON |
| PLANS. |
| THIS SHOUDL AHVE A MCB. |
| 225.31, FBC 106.1.2 |
| |
| 2) NOTE: PLEASE CORRELATE SIZES OF |
| PANELS ON PANEL SCHEDULES AND WHAT IS |
| BEING SHOWN ON RISER. |
| |
| 3) NOTE: PLEASE CORRELATE FEEDERS ON |
| RISER AND PANEL SCHEDULES. PLEASE SEE |
| 3/0, AND #1'S ETC FOR 100A BRKR FEED TO |
| THE SUB PANEL. |
| |
| |
| 4) NOTE: PLEASE SEE PANEL SCHEDULE |
| CIRCUTING DOES NOT SEEM TO START UNTIL |
| ABOUT 1/3 THE WAY DOWN THE PANEL. |
| PLEASE VERIFY THIS AS THIS IS NOT THE |
| WAY IT IS ON THE JOBSITE. |
| |
| |
| ** PLEASE KNOW, MANY ITEMS ON THE |
| JOBSITE DOES NOT MATCH WITH PLANS. |
| PLEASE KNOW, A PLAN REVIEW WAS DONE WITH |
| THE ELECTRICAL INPECTOR AND CONTRACTOR |
| ON THE PHONE AND MANY ITEMS SHOWN ON |
| THESE PLANS DO NOT MATCH WITH WHAT IS |
| INSTALLED IN FIELD. PLEASE GET WITH THE |
| CONTRACTOR AND VERIFY ALL. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |