Plan Review Notes For Permit 04120902
Permit Number 04120902
Review Stop E
Sequence Number 5
Notes
Date Text
2006-07-27 00:00:00**** UNSAT ******
  
 1) NOTE: PLEASE KNOW THAT THE PREVIOUS
 PLANS WERE REDLINED AS THE GENERATOR
 SHOWN ON PLANS WAS NOT PART OF THE
 PERMIT FOR THE HOUSE AND NO PERMIT TO
 DATE HAS BEEN APPLIED FOR THE
 RESIDENTIAL GEN. PLEASE REMOVE FROM
 PLANS.
 (SHOWS 5KW UNIT, IS THIS NOT A PRTABLE
 UNIT? )
  
 2) NOTE: PLEASE COMPLETE PANEL SCHEDULE
 WITH ALL CIRCUITS SPECIFIC TO AREAS AND
 ROOMS IN WHICH THEY FEED. PLEASE SEE
 408.4. IE, MASTER BEDRN LTS, LIVING RM
 RECEPTS, HALL LTS, ETC.
  
 3) NOTE: PLEASE SEE PLANS SHOWS A
 "TANKLESS" WATER HEATER FOR THE MAIN
 HOUSE. PLEASE SEE HOWEVER THE KW RATING
 SEEMS TO BE FOR A STANDARD WH UNIT.??
 PLEASE SEE TL WH'S FOR A HOUSE THIS SIZE
 IS TPICALLY MUCH LARGER. PLEASE VERIFY
 AND ADJUST LOAD CALCS.
 220
  
 4) NOTE: PLEASE SEE THERE ARE A FEW
 LOCATIONS ON PLANS WHERE LV UC PUCK LT
 ARE NOTED , HOWEVER HOW MANY AND
 LOCATIONS ARE NOT SHOWN. PLEASE CLARIFY.
  
 5) NOTE: PLEASE SHOW LOAD CALCULATIONS
 FOR PANELS A AND B. 215.5,220.31.
  
 6) NOTE: PLEASE CORRELATE RISER AND
 PANELS. PLEASE SEE RISER SHOWS 20CIRCUIT
 PANELS FOR "C" AND "B", HOWEVER THESE
 ARE SHOWN AS 40 CIRCUIT PANELS ON
 SCHEDULES.
  
 7) NOTE: PLEASE KNOW IF THESE PLANS ARE
 FOR FINAL WHICH THEY APPEAR TO BE.
 PLEASE SEE TAHT ANY "OPT" LISTED ON
 PLANS EITHER ARE IN OR ARE REMOVED AS
 OPTIONAL.
 PLANS SHALL CONTAIN AN ACCUREATE RECORD
 OF THE SCOPE OF WORK PERFORMED ON JOB
 SITE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  