2005-09-15 00:00:00 | BUILDING REVISION |
| DENIED |
| |
| |
| 1) BOTH SETS OF REVISED DRAWINGS ARE |
| REQUIRED TO BE SIGNED AND SEALED BY THE |
| ARCHITECT AND THE ENGINEER THAT SIGNED |
| AND SEALED THE ORIGINAL PLANS. FS 471 |
| AND 481. |
| |
| 2) REMOVE THE 4:12 ROOF PITCH INDICATION |
| FROM THE REAR GARAGE ELEVATION ON A5. |
| |
| 3) THE GARAGE FLOOR FRAMING PLAN ON S-7 |
| INDICATES A GARAGE WALL SECTION 1 ON S5. |
| THIS SECTION SPECIFIES A PITCHED ROOF. |
| PLEASE CORRECT. |
| |
| 4) SPECIFY THE SECOND FLOOR CEILING |
| INSULATION AS REQUIRED BY FBC CHAPTER |
| 13. MUST CORRESPOND TO ENERGY CALC. |
| FORMS. |
| |
| 5) SPECIFY ATTIC VENTILATION PER FBC |
| 2309.7. |
| |
| |
| |
| 6) ATTIC ACCESS IS NO LONGER REQUIRED |
| PER FBC 2309.6. REVISE SHEET A2 OR SHOW |
| THE 22" WIDE SPACE BETWEEN TRUSSES THAT |
| ARE 16"OC ON THE ROOF FRAMING PLAN ON |
| S7. |
| |
| 7) THE PARAPET DETAIL ON S8 SPECIFIES A |
| SIMPSON RT16 ATTACHED TO A CONCRETE BEAM |
| WITH TAPCONS. SIMPSON DOES NOT LIST THIS |
| CONNECTOR IN THEIR 2005 CATALOG. USP |
| DOES HAVE A RT16 CONNECTOR, HOWEVER IT |
| IS NOT SPECIFIED FOR ATTACHMENT TO |
| CONCRETE BEAMS. IF THERE IS A TECHNICAL |
| BULLETIN THAT SPECIFES THIS APPLICATION, |
| PLEASE SUBMIT TWO COPIES OR REVISE PLANS |
| TO SPECIFY A CONNECTOR DESIGNED AND |
| TESTED FOR THIS APPLICATION. |
| |
| 8) SPECIFY THE TYPE AND NUMBER OF |
| FASTENERS FOR THE SIMPSON U212 HANGER |
| SPECIFIED ON S8. SUBMIT THE FLORIDA |
| PRODUCT APPROVAL FOR THIS CONNECTOR. |
| |
| 9) SPECIFY THE WELD TYPE THAT WILL BE |
| USED TO ATTACH THE THREADED RODS TO THE |
| BRACKET IN DETAIL 4A ON S8. WHY ARE |
| THREADED RODS BEING USED RATHER THAN |
| NELSON STUDS. |
| |
| 10) THE ROOF DOWN SPOUTS SHALL DISCHARGE |
| AT LEAST 1 FOOT AWAY FROM THE STRUCTURE |
| SIDEWALL PER FBC 1503.4.4. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |