Plan Review Notes
Plan Review Notes For Permit 04120902
Permit Number 04120902
Review Stop B
Sequence Number 5
Notes
Date Text
2005-09-15 00:00:00BUILDING REVISION
 DENIED
  
  
 1) BOTH SETS OF REVISED DRAWINGS ARE
 REQUIRED TO BE SIGNED AND SEALED BY THE
 ARCHITECT AND THE ENGINEER THAT SIGNED
 AND SEALED THE ORIGINAL PLANS. FS 471
 AND 481.
  
 2) REMOVE THE 4:12 ROOF PITCH INDICATION
 FROM THE REAR GARAGE ELEVATION ON A5.
  
 3) THE GARAGE FLOOR FRAMING PLAN ON S-7
 INDICATES A GARAGE WALL SECTION 1 ON S5.
 THIS SECTION SPECIFIES A PITCHED ROOF.
 PLEASE CORRECT.
  
 4) SPECIFY THE SECOND FLOOR CEILING
 INSULATION AS REQUIRED BY FBC CHAPTER
 13. MUST CORRESPOND TO ENERGY CALC.
 FORMS.
  
 5) SPECIFY ATTIC VENTILATION PER FBC
 2309.7.
  
  
  
 6) ATTIC ACCESS IS NO LONGER REQUIRED
 PER FBC 2309.6. REVISE SHEET A2 OR SHOW
 THE 22" WIDE SPACE BETWEEN TRUSSES THAT
 ARE 16"OC ON THE ROOF FRAMING PLAN ON
 S7.
  
 7) THE PARAPET DETAIL ON S8 SPECIFIES A
 SIMPSON RT16 ATTACHED TO A CONCRETE BEAM
 WITH TAPCONS. SIMPSON DOES NOT LIST THIS
 CONNECTOR IN THEIR 2005 CATALOG. USP
 DOES HAVE A RT16 CONNECTOR, HOWEVER IT
 IS NOT SPECIFIED FOR ATTACHMENT TO
 CONCRETE BEAMS. IF THERE IS A TECHNICAL
 BULLETIN THAT SPECIFES THIS APPLICATION,
 PLEASE SUBMIT TWO COPIES OR REVISE PLANS
 TO SPECIFY A CONNECTOR DESIGNED AND
 TESTED FOR THIS APPLICATION.
  
 8) SPECIFY THE TYPE AND NUMBER OF
 FASTENERS FOR THE SIMPSON U212 HANGER
 SPECIFIED ON S8. SUBMIT THE FLORIDA
 PRODUCT APPROVAL FOR THIS CONNECTOR.
  
 9) SPECIFY THE WELD TYPE THAT WILL BE
 USED TO ATTACH THE THREADED RODS TO THE
 BRACKET IN DETAIL 4A ON S8. WHY ARE
 THREADED RODS BEING USED RATHER THAN
 NELSON STUDS.
  
 10) THE ROOF DOWN SPOUTS SHALL DISCHARGE
 AT LEAST 1 FOOT AWAY FROM THE STRUCTURE
 SIDEWALL PER FBC 1503.4.4.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  