Plan Review Notes
Plan Review Notes For Permit 04120902
Permit Number 04120902
Review Stop P
Sequence Number 3
Notes
Date Text
2005-04-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA STATUTES
  
 1) SHT E-2 SANITARY RISER DIAGRAM DOES
 NOT REFLECT THE FLOOR PLAN, NOR DOES IT
 MEET CODE REQUIREMENTS. CORRECT THE
 FOLLOWING:
 A) MINIMUM TRAP SIZE FOR THE WASH
 MACHINE IS 2". TABLE 709.1
 B) A CLEANOUT 4' ABOVE THE FLOOR IS
 REQUIRED FOR THE WASH MACHINE. SECTION
 708.10.
 C) A STANDPIPE IS REQUIRED ON THE WASH
 MACHINE. SECTION 1002.1.
 D) BATH #3 A CROSS FITTING IS NOT
 APPROVED BETWEEN THE LAV AND TUB.
 SECTION 706.3.
 E) BATH #2 SHOWS A TUB ON THE FLOOR
 PLAN, BUT IS SHOWN AS A SHOWER ON THE
 RISER DIAGRAM. SECTION 104.2.1.
 F) CROSS BETWEEN THE WATER CLOSET AND
 THE SHOWER IN THE MASTER BATH IS NOT
 APPROVED. SECTION 706.3.
 G) DRY HORIZONTAL VENT IN THE MASTER
 BATH UPSTREAM OF THE TUB IS NOT
 APPROVED. SECTIONS 905.3 & 905.4.
 H) POWDER ROOM ON THE FIRST FLOOR OF
 THE CABANA SHOWN ON THE FLOOR PLAN IS
 NOT SHOWN ON THE RISER DIAGRAM. SECTION
 104.2.1.
 I) SEE EXAMPLES ON RISER DIAGRAM IN RED
 SHOWING HOW TO CORRECT RISER TO MEET
 CODE REQUIREMENTS AND REFLECT THE FLOOR
 PLAN.
 2) SEE ATTACHED SHEET CONCERNING THE
 DESIGN PROFESSIONAL AND FS 553.80(2)(B)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]