2005-04-12 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FLORIDA STATUTES |
| |
| 1) SHT E-2 SANITARY RISER DIAGRAM DOES |
| NOT REFLECT THE FLOOR PLAN, NOR DOES IT |
| MEET CODE REQUIREMENTS. CORRECT THE |
| FOLLOWING: |
| A) MINIMUM TRAP SIZE FOR THE WASH |
| MACHINE IS 2". TABLE 709.1 |
| B) A CLEANOUT 4' ABOVE THE FLOOR IS |
| REQUIRED FOR THE WASH MACHINE. SECTION |
| 708.10. |
| C) A STANDPIPE IS REQUIRED ON THE WASH |
| MACHINE. SECTION 1002.1. |
| D) BATH #3 A CROSS FITTING IS NOT |
| APPROVED BETWEEN THE LAV AND TUB. |
| SECTION 706.3. |
| E) BATH #2 SHOWS A TUB ON THE FLOOR |
| PLAN, BUT IS SHOWN AS A SHOWER ON THE |
| RISER DIAGRAM. SECTION 104.2.1. |
| F) CROSS BETWEEN THE WATER CLOSET AND |
| THE SHOWER IN THE MASTER BATH IS NOT |
| APPROVED. SECTION 706.3. |
| G) DRY HORIZONTAL VENT IN THE MASTER |
| BATH UPSTREAM OF THE TUB IS NOT |
| APPROVED. SECTIONS 905.3 & 905.4. |
| H) POWDER ROOM ON THE FIRST FLOOR OF |
| THE CABANA SHOWN ON THE FLOOR PLAN IS |
| NOT SHOWN ON THE RISER DIAGRAM. SECTION |
| 104.2.1. |
| I) SEE EXAMPLES ON RISER DIAGRAM IN RED |
| SHOWING HOW TO CORRECT RISER TO MEET |
| CODE REQUIREMENTS AND REFLECT THE FLOOR |
| PLAN. |
| 2) SEE ATTACHED SHEET CONCERNING THE |
| DESIGN PROFESSIONAL AND FS 553.80(2)(B) |
| |
| REVIEW BY KEN STEVENS |