Plan Review Notes For Permit 04120902 |
Permit Number |
04120902 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2005-04-14 00:00:00 | DENIED | | | | 1) SUBMIT A COPY OF THE PAID RECEIPT FOR | | THE COUNTY IMPACT FEES. | | | | 2) THE STRUCTURE IS LOCATED IN AN "A5" | | FLOOD ZONE. AN ELEVATION CERTIFICATE | | WILL BE REQUIRED. | | | | 3) THE OWNER/AGENT IS REQUIRED TO SIGN | | AND DATE THE ENERGY CALCULATION FORMS | | FOR BOTH STRUCTURES. | | | | 4) SHOP DRAWINGS WILL BE REQUIRED FOR | | THE ALUMINUM GUARDRAILS. | | | | 5) SHEET A1 OF THE PLANS SPECIFIES | | IMPACT GLAZING FOR THE STRUCTURE. REMOVE | | THE PRODUCT APPROVALS FOR THE NON-IMPACT | | WINDOWS AND DOORS. | | | | 6) SUBMIT FLORIDA PRODUCT APPROVALS FOR | | THE CONC."S" TILE ROOF. | | | | 7) SUBMIT PRODUCT FLORIDA APPROVALS FOR | | THE ROOFING MATERIAL FOR THE FLAT | | PORTIONS OF THE ROOF THAT WILL NOT BE | | COVERED WITH TILE. | | | | 8) THE NOA SUBMITTED FOR THE MODIFIED | | BITUMEN ROOFING FOR INSTALLATION UNDER | | THE MECHANICALLY FASTENED TILE DOES NOT | | CORRESPOND WITH THE NOA ATTACHED TO IT. | | SUBMIT THE CORRECT NOA. | | | | 9) THE NOAS SUBMITTED WITH THE STATE | | PRODUCT APPROVALS FOR THE PGT FD101 | | DOORS AND THE SH 701 AND PW 701 WINDOWS | | DO NOT CORRESPOND. THE CORRECT NOA | | NUMBERS ARE LISTED ON THE FL PRODUCT | | COVER SHEET. | | | | IF YOU HAVE QUESTIONS PLEASE CALL: | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 |
|