Plan Review Notes For Permit 04120902 |
Permit Number |
04120902 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-03-09 00:00:00 | DENIED | | | | 1) SUBMIT A COPY OF THE PAID RECEIPT FOR | | THE COUNTY IMPACT FEES. | | | | 2) STRUCTURE IS LOCATED IN AN "A5" FLOOD | | ZONE. | | | | 3) THE SUBSURFACE SOIL INVESTIGATION | | REPORT HAS THE WRONG ADDRESS. | | | | 4) THE OWNER/AGENT IS REQUIRED TO SIGN | | THE ENERGY CALC.FORMS FOR THE GAME ROOM. | | | | 5) SHOP DRAWINGS FOR THE ALUMINUM | | GUARDRAILS WILL BE REQUIRED. | | | | 6) THE DOOR FROM THE EGRESS STAIRS CAN | | NOT OPEN INTO THE GARAGE. FBC 1001.1.3 | | REQUIRES AN UNOBSTRUCTED PATH OF TRAVEL | | TO THE EXTERIOR OF THE BUILDING. THE | | MEANS OF EGRESS SHALL NOT BE THROUGH | | KITCHENS, CLOSETS, RESTROOMS OR SIMULAR | | AREAS. | | | | 7) FLORIDA PRODUCT APPROVAL COVER SHEETS | | HAVE NOT BEEN PROVIDED FOR ALL OF THE | | PRODUCTS THAT WERE SUBMITTED. SOME OF | | THE FL PRODUCT COVERS DO NOT CORRESPOND | | TO THE NOAS SUBMITTED. THE INFORMATION | | SUBMITTED MUST MATCH THE INFORMATION | | LISTED ON THE STATE WEBSITE. SEE THE | | NOTES ON THE PRODUCT APPROVALS THAT WERE | | SUBMITTED. TWO COPIES OF EVERYTHING IS | | REQUIRED. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CALL: | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 |
|