Plan Review Notes For Permit 04120902 |
Permit Number |
04120902 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-12-27 00:00:00 | PLUMBING PLAN REVIEW DENIED | | PLUMBINGT RISER DIAGRAM NOT TO CODE AND | | CANNOT BE INSTALLED AS DRAWN.SHOW ON | | RISER DIAGRAM WHERE 3" RISES ARE TO BE | | INSTALLED.MASTER BATHROOM, LAV'S ARE ON | | DIFFERENT WALL CAN NOT US SAMEVENT | | STACK. THERE IS NO PVC FITTING FOR | | MASTER BATH CIRCLED IN RED. BATH | | #2MARKED ON RISER DIAGRAM AS MST BATH, | | THERE IS NO SHR. IN BATH # 2 AND THE | | LAVS. ARE TOO FAR APART TO BE ON SAME | | STACK. BATH NUMBER # 3 THE WET BAR IS | | NOT ON SAME WALL AS LAV. ADDITIONAL | | STACK REQUIRED. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|