Plan Review Notes
Plan Review Notes For Permit 04120902
Permit Number 04120902
Review Stop E
Sequence Number 1
Notes
Date Text
2004-12-23 00:00:00********** UNSAT ****************
  
  
 1) NOTE: PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
  
 2)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 COMMON TEXT NOTE: PLEASE SEE MISSING SD
 LEADING TO FLR ABOVE.
  
  
 3)NOTE: PLEASE SHOW GROUNDING ELETRODE
 SYSTEM PER 250.50. FOOTER STEEL/COLD
 WATER/ ETC. SIZE ALL PER 250.66
 SHOWN AS #4
  
  
 4)NOTE: PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12` RULE.
  
  
 5) NOTE: PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52E MISSING FRONT.
  
  
 6)NOTE: PLEASE SEE RECEPTS SERVING
 KITCHEN COUNTERSPACE TO MEET 210.52C-
 SEC'S 1,2,3,4 AND 5
 PLEASE SEE MISSING.
  
 7)NOTE: PLEASE SPACING FOR A/C DISC'S
 PER 110.26
  
 8)NOTE: PLEASE VERIFY KW LOAD SHOWN FOR
 WATER HEATER AND OVENS. WH IS SHOWN AS
 80 GAL YET ONLY SHOWS 5KW HEAT?
 PLEASE ALSO SEE DOUBLE OVENS ARE SHOWN
 WITH 50A OCP YET TWO OVENS ARE ONLY
 SHOWN WITH 6KW LOAD??
 PLEASE VERIFY THE ABOVE AND ADJUST AS
 NEEDED.
  
 9)NOTE: PLEASE PROVIDE ROOM
 DESIGNATIONS
 ON PLANS.
  
 10)NOTE: PLEASE INDICATE GFI FOR
 JACUZZI/SPA TUB. PER 680
  
  
 11 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY
 NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 12)NOTE: PLEASE SEE ZONING COMMENTS FOR
 APT AREA SHOWN ABOVE GARAGE.
 THIS WILL AFFECT ELECTRICAL PLANS.
  
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD SHOULD BE SUBMITTED FOR
 REFERENCE ONLY.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved