Date |
Text |
2004-12-23 00:00:00 | ********** UNSAT **************** |
| |
| |
| 1) NOTE: PLEASE LIST ALL THE REQ'D |
| DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| SCHEDULE. PER 210.52D, 210.11C3 |
| |
| |
| 2)NOTE: SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| UNIT. |
| IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| TO FLOORS ABOVE AND IN THE VICINITY OF |
| BEDROOMS. |
| PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| A MIN OF 3' FROM BATHROOM DOORS AND |
| KITCHENS. |
| ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| COMMON TEXT NOTE: PLEASE SEE MISSING SD |
| LEADING TO FLR ABOVE. |
| |
| |
| 3)NOTE: PLEASE SHOW GROUNDING ELETRODE |
| SYSTEM PER 250.50. FOOTER STEEL/COLD |
| WATER/ ETC. SIZE ALL PER 250.66 |
| SHOWN AS #4 |
| |
| |
| 4)NOTE: PLEASE SHOW OUTLET SPACING PER |
| 210.52. 2',6`,12` RULE. |
| |
| |
| 5) NOTE: PLEASE SEE MISSING RECEPTS FOR |
| FRONT AND/OR REAR OF DWELLING. |
| 210.52E MISSING FRONT. |
| |
| |
| 6)NOTE: PLEASE SEE RECEPTS SERVING |
| KITCHEN COUNTERSPACE TO MEET 210.52C- |
| SEC'S 1,2,3,4 AND 5 |
| PLEASE SEE MISSING. |
| |
| 7)NOTE: PLEASE SPACING FOR A/C DISC'S |
| PER 110.26 |
| |
| 8)NOTE: PLEASE VERIFY KW LOAD SHOWN FOR |
| WATER HEATER AND OVENS. WH IS SHOWN AS |
| 80 GAL YET ONLY SHOWS 5KW HEAT? |
| PLEASE ALSO SEE DOUBLE OVENS ARE SHOWN |
| WITH 50A OCP YET TWO OVENS ARE ONLY |
| SHOWN WITH 6KW LOAD?? |
| PLEASE VERIFY THE ABOVE AND ADJUST AS |
| NEEDED. |
| |
| 9)NOTE: PLEASE PROVIDE ROOM |
| DESIGNATIONS |
| ON PLANS. |
| |
| 10)NOTE: PLEASE INDICATE GFI FOR |
| JACUZZI/SPA TUB. PER 680 |
| |
| |
| 11 )NOTE: PLEASE SEE 220.3B4. |
| PLEASE SHOW ALL RECESSED LTS BASED ON |
| MAX WATTAGE FOR FIXTURE(S). THIS MAY |
| NOT |
| BE FIGURED IN W/ 3W/PER SQ FT. |
| PLEASE PROVIDE FIXTURE INFORMATION ON |
| LEGEND. |
| |
| 12)NOTE: PLEASE SEE ZONING COMMENTS FOR |
| APT AREA SHOWN ABOVE GARAGE. |
| THIS WILL AFFECT ELECTRICAL PLANS. |
| |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO TWO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| ONE SET OF OLD SHOULD BE SUBMITTED FOR |
| REFERENCE ONLY. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |