2005-01-07 00:00:00 | DENIED |
| 1)IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| |
| 2) STRUCTURE IS LOCATED IN AN "A5" FLOOD |
| ZONE AN ELEVATION CERTIFICATE WILL BE |
| REQUIRED. THE MINIMUM ELEVATION IS |
| 7.5',WHICH INCLUDES AN ADDITIONAL 6" |
| ABOVE BASE FLOOD ELEVATION PER CITY OF |
| WPB ORDINANCE. |
| |
| 3) FBC* 1804.2.2AREA OF QUESTIONABLE |
| SOIL.SUBMIT A GEOTECHNICAL REPORT |
| TO VERIFY THE SAFE BEARING CAPACITY OF |
| THE SOIL. |
| |
| 4) THE OWNER/AGENT IS REQUIRED TO SIGN |
| THE ENERGY CALC. FORM. THE SQUARE |
| FOOTAGE OF CONDITIONED SPACE ON THE FORM |
| DOES NOT AGREE WITH THE AMOUNT SPECIFIED |
| ON THE PLANS. SECTION A ON S4 AND THE |
| ENERGY CALC. INFO ON A1 SPECIFIES FOAM |
| BOARD INSULATION AND THE ENERGY CALCS. |
| LIST R-4.1.PLEASE CORRECT. |
| |
| 5) SPECIFY ON THE PLANS THAT THE |
| INTERMEDIATE RAILS OF THE GUARDRAILS AT |
| THE STAIRS AND BALCONIES ARE REQUIRED TO |
| REJECT A 4" SPHERE AND THE BOTTOM RAIL |
| SHALL REJECT A 2" SPHERE. SEE FBC 1015.3 |
| |
| |
| 6) SPECIFY FIREBLOCKING AT THE ENCLOSED |
| SPACES BETWEEN STAIR STRINGERS AT THE |
| TOP AND BOTTOM OF RUNS. SEE FBC |
| 2305.1.4 |
| |
| 7) THE STAIR CALCS ON A1 AND A2 CONTAIN |
| ERRORS. PLEASE CORRECT. |
| |
| 8) SHOP DRAWINGS WILL BE REQUIRED FOR |
| THE ALUMINUM GUARDRAILS AT THE STAIRS |
| AND BALCONIES. |
| |
| 9) THE CITY OF WPB AMENDMENTS TO FBC |
| TABLE 2306.1 REQUIRES ROOF SHEATHING TO |
| BE NAILED AT 4"OC AT EDGES AND 6"OC |
| INTERMEDIATE IN ZONE THREE WITH 8D RING |
| SHANK NAILS WHEN MEAN ROOF HEIGHT IS |
| 25'-35'. THE OUTSIDE CORNERS OF HIP |
| ROOFS ARE ZONE 3. |
| |
| 10) FBC 1006.2.4 REQUIRES THE WALLS |
| ADJACENT TO THE EXTERIOR EXITWAY STAIRS |
| AND COVERED PORCH TO HAVE A ONE HOUR |
| RATING WITH OPENING PROTECTIVES. |
| |
| 11) SUBMIT MANUFACTURER'S SPECS. AND |
| LISTING INFORMATION FOR THE BUILT-IN |
| GAS |
| BBQ. |
| |
| 12) THE PLANS SHOW VENTED PREFAB |
| FIREPLACES WITH FLUES TO THE ROOF. THE |
| PRODUCT APPROVAL SUBMITTED IS FOR |
| VENTLESS FIREPLACES. PLEASE CLARIFY. |
| |
| 13) FBC 1707.4.4.2 REQUIRES WINDOW AND |
| DOOR FRAMES TO BE FASTENED THROUGH 1X |
| BUCKS AND INTO THE STRUCTURAL SUBSTRATE. |
| PLEASE CORRECT BUCK NOTE ON A1. |
| |
| 14) PROVIDE A FOOTING DETAIL AT THE |
| GARAGE DOOR OPENING. |
| |
| 15) THE SPECIFIED THICKNESS OF THE |
| FOOTER IN DETAIL G ON S1 IS NOT |
| CORRECT. |
| |
| 16) PRODUCT APPROVALS SUBMITTED |
| WITH PERMIT APPLICATION AFTER OCTOBER 1, |
| 2003 ARE REQUIRED TO COMPLY WITH THE |
| FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| INFORMATION PLEASE SEE THE STATE WEBSITE |
| AT WWW.FLORIDABUILDING.ORG. PRODUCTS |
| WITH STATEWIDE APPROVAL ARE REQUIRED TO |
| BE SUBMITTED WITH A COVER SHEET THAT |
| LISTS THE PRODUCT IDENTITY NUMBER FROM |
| THE STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. |
| |
| 17) SUBMIT (2) COMPLETE, CLEAN AND |
| LEGIBLE COPIES OF PRODUCT APPROVALS. |
| THE FOLLOWING SUBMITTALS HAVE SOME PAGES |
| THAT ARE ILLEGIBLE: |
| - PGT PW 701 |
| - WINDSOR GARAGE DOOR |
| - MULE-HIDE ROOFING |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |