Plan Review Notes For Permit 04120898 |
Permit Number |
04120898 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-01-03 00:00:00 | DENIED: | | 1.PROVIDE OUTSIDE AIR CALCULATIONS | | PER | | 2001 FBC(M) TABLE 430.3. | | | | 2.PROVIDE OUTSIDE AIR DUCT SIZE, | | MATERIAL, AND INTAKE.PLEASE NOTE | | INTAKES SHALL NOT BE LOCATED WITHIN 10 | | FT FROM LOT LINES OR BUILDINGS ONTHE | | SAME LOT.INTAKES SHALL BE LOCATED AS | | NOT TO RECIRCULATE NOXIOUS CONTAMINANTS | | FROM PARKING LOTS, LOADING DOCKS STREETS | | AND ALLEYS, | | | | 3.PLAN INDICATES AHU 3 LOCATED IN AN | | ELECTRICAL ROOM.DOES THIS ROOM HAVE A | | FIRE RESISTANCE RATING?SHOULD THIS BE | | THE FPL VAULT, NO AHU WILLNOT BE | | ALLOWED.PROVIDE MANUFACTURER SUBMITTAL | | & INSTALLATION INSTRUCTIONS FOR THE FIRE | | DAMPERS ON THE JOBSITE AT THE TIME OF | | INSPECTION. | | | | 4.CLARIFY ELECTRICAL ROOM OFF THE | | STAIRWELL.IS THIS BELOW THE STAIRS? | | | | 5. PROVIDE CONDENSATE LAYOUT, PIPE | | MATERIAL, SIZE AND TERMINATION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|