2005-01-03 00:00:00DENIED:
 1.PROVIDE OUTSIDE AIR CALCULATIONS
 PER
 2001 FBC(M) TABLE 430.3.
  
 2.PROVIDE OUTSIDE AIR DUCT SIZE,
 MATERIAL, AND INTAKE.PLEASE NOTE
 INTAKES SHALL NOT BE LOCATED WITHIN 10
 FT FROM LOT LINES OR BUILDINGS ONTHE
 SAME LOT.INTAKES SHALL BE LOCATED AS
 NOT TO RECIRCULATE NOXIOUS CONTAMINANTS
 FROM PARKING LOTS, LOADING DOCKS STREETS
 AND ALLEYS,
  
 3.PLAN INDICATES AHU 3 LOCATED IN AN
 ELECTRICAL ROOM.DOES THIS ROOM HAVE A
 FIRE RESISTANCE RATING?SHOULD THIS BE
 THE FPL VAULT, NO AHU WILLNOT BE
 ALLOWED.PROVIDE MANUFACTURER SUBMITTAL
 & INSTALLATION INSTRUCTIONS FOR THE FIRE
 DAMPERS ON THE JOBSITE AT THE TIME OF
 INSPECTION.
  
 4.CLARIFY ELECTRICAL ROOM OFF THE
 STAIRWELL.IS THIS BELOW THE STAIRS?
  
 5. PROVIDE CONDENSATE LAYOUT, PIPE
 MATERIAL, SIZE AND TERMINATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.