Plan Review Notes For Permit 04120838 |
Permit Number |
04120838 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-01-03 00:00:00 | FIRE REVIEW - DENIED | | | | 1) WHEN THE FIRE ALARM CONTROL UNIT | | PANEL IS REPLACED IN AN EXISTING SYSTEM, | | IT WILL BE TREATED AS A NEW SYSTEM. | | | | 2) NEW FIRE ALARM SYSTEMS SHALL BE UL | | LISTED FOR CENTRAL STATION SERVICE. | | | | 3) ALL NEW FIRE ALARM SYSTEMS THAT | | SUPERVISE FIRE SPRINKLER SYSTEMS SHALL | | BE UL CERTIFICATED AND HAVE DOCUMENTS | | ATTESTING TO THIS CERTIFICATION PRIOR TO | | FINAL APPROVAL OF THE FIRE ALARM | | SYSTEM. | | | | 4) THE FIRE ALARM SYSTEM SHALL BE CLASS | | "A" OR FULLY ADDRESSABLE. | | | | | | NATE MCCRAY, CAPTAIN | | 561-835-2910 OR 561-805-6722 |
|