Plan Review Notes
Plan Review Notes For Permit 04120830
Permit Number 04120830
Review Stop P
Sequence Number 3
Notes
Date Text
2005-10-01 00:00:00DENIED;
 1.WATER RISER DIAGRAMS;
 ,
 SHOCK ARRESTORS REQ. ON KITCHEN AND
 WASHING MACHINE SEC.604.9 (ALL 4 RD'S)
 THERMAL EXPANSION TANKES, PER.
 MANUFACTUES INSTALLATION INSTRUCTIONS
 TANK TO BE ON COLD WATER. ALL (4RD'S)
 SHUTOFF VALVES REQUIRED FOR EACH UNIT
 SHOW ON RISER DIAGRAM
 WATER RISER DIAGRAM 2ND FLOOR REAR W/M
 NOT SHOWN. ONE PLAN MARKED IN RED
 2. SANITARY RISER DIAGRAMS;
 W/C FIRST FL NOT IN BATHROOM GROUP.
 2ND FL. ONLY A SHOWER ON FL PLAN NO
 TUB.
 1ST AND 2ND FL MISSING W/M'S
 BACK BUILDING, 4 BATHROOMS SHOWN ONLY
 TWO ON FLOOR PLAN.
 W/M'S NOT SHOWN ON RISER DIAGRAM.
 3.WATER HEATERS ON PLANS 5 ARE SHOWN
 PLEASE DELETE ONE.
 4. SEE NOTE 15 BUILDING PLAN REVIEW.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  
  
  
  