2005-09-19 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2001 |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| TO THE FBC2001 |
| |
| THE FOLLOWING COMMENTS ARE FROM THE |
| PREVIOUS REVIEW.NUMBERING WILL REMAIN |
| THE SAME TO MAINTAIN CONSISTENCY. |
| |
| ALL CHANGES TO THE PLAN ARE TO BE |
| CLOUDED. |
| |
| 1.)SEE PROPERTY APPRAISER VALUATION |
| ATTACHED.THIS IS AN OVER 50% |
| IMPROVEMENT AND MUST COMPLY WITH |
| FBC3401.7.2.6.THIS SECTION AFFECTS |
| OTHER COMMENTS ON THIS LIST. (WAS |
| ACKNOWLEDGED.) |
| |
| 2.)ADDRESSED. |
| |
| 3.)THIS APPEARS TO BE TWO UNITS; ONE |
| UPSTAIRS, ONE DOWNSTAIRS.2ND FLOOR IS |
| TO BE IMPACT GLASS, CITY OF WEST PALM |
| BEACH IMPLEMENTATION STANDARD FOR |
| HURRICANE MISSILE IMPACT PROTECTION, |
| ITEM #13, SEE ATTACHED.SUBMIT A |
| HURRICANE INSTALLATION PLAN INCLUDING |
| WHERE THE SHUTTERS WILL BE STORED FOR |
| SHUTTERS USED ON THE FIRST FLOOR. |
| |
| SECOND REVIEW COMMENT - THIS WAS |
| ADDRESSED BY CHANGING THE |
| SECOND FLOOR TO IMPACT AND A NOTE |
| STATING THAT THE FIRST FLOOR SHUTTERS |
| WOULD BE STORED IN THE UTILITY ROOM |
| BELOW THE STAIRS.ONLY THE BUILDING |
| OFFICIAL CAN APPROVE THE USE OF SHUTTERS |
| ON A COMMERCIAL BUILDING.PLEASE SUBMIT |
| A HURRICANE SHUTTER INSTALLATION PLAN |
| FOR REVIEW.THIS IS TO INCLUDE ALL |
| PERTINENT INFORMATION SUCH AS STORAGE |
| LOCATION, SIZE OF STORAGE AREA, WHERE |
| THEY ARE STORED IN THAT AREA, HOW THEY |
| ARE SECURED IN THAT LOCATION; WHO IS TO |
| INSTALL THEM; TIME ESTIMATE FOR |
| INSTALLATION; WHEN THE SHUTTERS WILL BE |
| INSTALLED, ETC.THIS MAY BE SUBMITTED |
| SEPARATELY FROM PLAN REVIEW (NO FEE). |
| |
| PLAN WAS NOT CHANGED, STILL SHOWS |
| SHUTTERS ON THE FIRST FLOOR, AND AN |
| INSTALLATION WAS NOT SUBMITTED FOR |
| REVIEW. |
| |
| 4.)THE BALCONY (MEANS OF EGRESS FOR |
| 2ND FLOOR UNIT) IS TO COMPLY WITH |
| FBC1014.1.SHOW FIRE RESISTANCE (UL |
| ASSEMBLY OR CALCULATED FBC CHAPTER 7), |
| PROVIDE DOOR FIRE RATING INFORMATION. |
| |
| SECOND REVIEW COMMENT - THE FIRE RATING |
| FOR THE DOOR WAS |
| PROVIDED.I BELIEVE THAT THIS WAS |
| ADDRESSED BY SHOWING TWO LAYERS OF |
| DRYWALL ON THE CEILING OF THE FIRST |
| FLOOR UNIT.PROVIDE CALCULATED FIRE |
| RESISTANCE FOR THE FLOOR/CEILING |
| ASSEMBLY FBC709 (EACH COMPONENT AND |
| TIME, SHOW TOTAL). |
| |
| UL L504 WAS SHOWN ON THE PLAN.PLEASE |
| INCORPORATE A DETAIL INTO THE PLAN. |
| |
| 5.)THE EXTERIOR STAIR IS TO COMPLY |
| WITH FBC1006.2.4.SHOW FIRE RESISTANCE |
| OF THE WALL.OPENINGS WITHIN 10' ARE |
| TO BE 3/4 HR.INDICATE ON THE PLAN. |
| |
| SECOND REVIEW COMMENT - FIRE RESISTANCE |
| OF THE WALL REQUIRED BY |
| FBC1006.2.4 WAS NOT SHOWN.THERE IS A |
| NOTE ON THE PLAN REGARDING OPENINGS.IT |
| IS THE RESPONSIBILITY OF THE DESIGNER TO |
| DETERMINE WHICH OPENINGS ARE TO BE |
| PROTECTED.INDICATE ON THE ELEVATIONS, |
| FLOOR PLAN OR A SCHEDULE. ALSO INCLUDE |
| THE REAR BUILDING.SHOW RATED WALL |
| REQUIREMENT ON THE FLOOR PLAN AS WELL AS |
| A DETAIL SHOWING HOW IT COMPLIES. |
| |
| UL DESIGN U301 WAS SPECIFIED FOR THE NEW |
| WALL.INCORPORATE THE DESIGN FOR FIRE |
| RESISTANT WALLS INTO YOUR PLAN.YOUR |
| WALL SECTION IS IN CONFLICT WITH THIS |
| DETAIL.ALSO U301 HAS DRYWALL ON BOTH |
| SIDES; APPEARS TO BE AN INTERIOR BEARING |
| WALL, YOUR PLAN REQUIRES AN EXTERIOR |
| APPLICATION WHICH MUST ALSO HAVE |
| STRAPPING TO COMPLY WITH WIND |
| REQUIREMENTS.PLEASE CLARIFY. |
| |
| HOW DOES THE EXISTING WALL COMPLY WITH |
| THIS REQUIREMENT?ACCORDING TO THE |
| ENERGY CALCS, THIS IS A FRAME WALL. |
| PROVIDE A DETAIL AND SHOW COMPLIANCE. |
| |
| NOTE THAT FIRE RESISTANT WINDOWS REQUIRE |
| IMPACT PROTECTION.THIS OPENING SHOULD |
| BE INCLUDED IN THE PROPOSAL TO THE |
| BUILDING OFFICIAL, INCLUDING HOW THE |
| SECOND FLOOR WILL BE ACCESSED FOR |
| INSTALLATION. |
| |
| 6.)ADDRESSED. |
| |
| 7.)ADDRESSED. |
| |
| 8.)ADDRESSED. |
| |
| 9.)FOR THE MODIFIED ROOF, INDICATE |
| WHICH METHOD OF INSTALLATION YOU ARE |
| USING. |
| |
| SECOND REVIEW - THIS SHOULD BE DONE BY |
| CHOOSING ONE OF |
| THE APPROVED ASSEMBLIES ON THE PRODUCT |
| APPROVAL. |
| |
| NOT ADDRESSED.IF THIS IS NOT ADDRESSED |
| CORRECTLY PRIOR TO PERMIT ISSUANCE, THE |
| ROOF PERMIT NUMBER WILL BE VOIDED AND A |
| SEPARATE PERMIT WITH SEPARATE FEES AND |
| REVIEW WILL BE REQUIRED. |
| |
| 10.)ADDRESSED. |
| |
| 11.)BATHROOM DOOR ON THE FIRST FLOOR |
| IS TO COMPLY WITH FBC11-11(1), CLEAR |
| OPENING OF AT LEAST 29IN. |
| |
| NEW COMMENT - THIS IS REQUIRED ON SECOND |
| FLOOR BATHROOMS AS WELL.PLEASE REVISE. |
| |
| 12.)THE ELEVATIONS AND WALL SECTION DO |
| NOT MATCH.IS THERE A PARAPET WALL?IF |
| THERE IS, SHOW DRAINAGE FBC1503.4. |
| |
| NOT ADDRESSED.A NOTE WAS SENT THAT |
| THIS IS EXISTING.PLEASE SEE COMMENT |
| #1.SHOW ALL REQUIRED DRAINAGE WITH |
| CALCULATIONS. |
| |
| 13.)SUBMIT PRODUCT APPROVALS AND FIRE |
| RESISTANCE INFORMATION IF APPLICABLE FOR |
| THE FOLLOWING: |
| |
| EXTERIOR DOOR, FIRE RATED |
| SINGLE HUNG WINDOW, FIRE RATED |
| IMPACT SINGLE HUNG WINDOWS |
| |
| 14.)THE ENERGY CALCS FOR THE FRONT |
| BUILDING, 1ST FLOOR GIVES A SQUARE FOOT |
| AREA OF1203, THE LETTER FROM THE |
| ENGINEER GIVES AN AREA OF 1483.SECOND |
| FLOOR ENERGY CALCS GIVES AN AREA OF 965, |
| LETTER FROM ENGINEER STATES 685 AFTER |
| THE ADDITION.PROVIDE AREA CALCS FOR |
| THE REAR BUILDING, 1ST AND 2ND FLOORS. |
| PLEASE COMPARE WITH ENERGY CALCS PRIOR |
| TO RESUBMITTAL. |
| |
| 15.)THE LETTERHEAD FOR THE ENGINEER IS |
| REQUIRED TO HAVE THE CERTIFICATE OF |
| AUTHORIZATION, FAC61G15. |
| |
| 16.)SEE ATTACHED FS553.80(2)(B).A 4X |
| PLAN REVIEW FEE WILL BE CHARGED IF |
| COMMENTS ARE NOT ADDRESSED. |