2005-07-11 00:00:00 | ********* UNSAT 2ND REVIEW ********** |
| |
| PLEASE SEE SOME NOTES FROM PREVIOUS |
| REVIEW STILL NEED TO BE ADDRESSED. |
| |
| 1)NOTE: NOTE #1, OK, AIC CALCS SHOWN. |
| |
| 2)NOTE: NOTE #2 NO, |
| PLEASE SEE 310.16,240.4, AND 250.66 FOR |
| SIZING. |
| |
| 3)NOTE: NOTE #3 OK. |
| |
| 4)NOTE: NOTE #4 NO, SERVICE IS NOW SHOWN |
| TO BE LOCATED ON FRONT BLDG, HOWEVER NO |
| INFORMATION FOR MAINS AT DETACHED BLDG. |
| PLEASE SEE 225.32, 225.34 |
| GROUNDING PER 250.32 |
| |
| 5)NOTE: NOTE #5 OK, HOWEVER PLEASE SEE |
| NEWNOTE; |
| |
| 6)NOTE: NOTE #6 NO, CU'S AND CU'S DISC'S |
| SHOWN, HOWEVER PLEASE SEE AHU'S AND |
| MISSING AHU'S DISC'S. |
| |
| 7)NOTE: NOTE #7 NO, PLEASE SEE PREVIOUS. |
| 310.16,240.4 |
| |
| 8)NOTE: NOTE #8 OK. |
| SEE NOTE #4 FOR GROUNDING AT DETACHED |
| BLDGS. |
| |
| 9)NOTE: NOTE #9 OK, HOWEVER PLEASE SEE |
| NOTE MENTIONS DEVICES TO BE ARC FAULT |
| TYPE? PLEASE SEE THESE DEVICES ARE NOT |
| MADE AS ARC FAULT PROTECTIVE TYPES. |
| PLEASE SEE 210.12 UNDER 2002 NEC, THIS |
| REQUIRES THE ENTIRE BRANCH CIRCUIT TO |
| HAVE ARC FAULT PROTECTION. THE BREAKER |
| AT PANEL IS THE ONLY WAY ARC FAULT |
| PROTECTION CAN BE PROVIDED. |
| |
| 10)NOTE: NOTE #10 OK. |
| |
| 11)NOTE: NOTE #11 OK. |
| |
| NEW NOTES. |
| |
| 1)NOTE: PLEASE SEE MISSING KITCHEN |
| COUNTERSPACE GFI PER 210.52C1, PLEASE |
| SEE LOWERE AND UPPER UNITS. |
| |
| 2)NOTE: PLEASE SEE MISSING SD EITHER |
| INSIDE OR OUTSIDE BEDRM #1 ON FIRST FLR |
| UNIT. PLEASE SEE NFPA-72 8-1.4.1.6.2, |
| WHICH REQUIRES SD'S IN THE IMMEDIATE |
| VICINITY OUTSIDE BEDRMS. |
| |
| 3)NOTE: PLEASE SEE MISSING RECEPT FOR 2' |
| OF WALL SPACE IN LIV RM FIRST FLR. |
| 210.52 |
| |
| 4)NOTE: PLEASE SEE ANY HAND WRITTEN |
| CHANGES TO PLANS AND SCOPE SHOULD BE |
| SIGNED AND DATED BY ENGINEER ALSO. FS |
| 471.025 |
| |
| 5)NOTE: PLEASE SEE COPY OF FS |
| 553.80(2)(B) WITH RESPECT TO DESIGN |
| PROFESSSIONAL(S) AND PLANS WITH REPEAT |
| COMMENTS THREE OR MORE TIMES. THIS IS A |
| NOTICE ONLY GIVEN AT THIS TIME. |
| |
| 6)NOTE: PLEASE SEE NOC HAS EXPIRED AND |
| NEEDS TO BE RE-RECORDED. PLEASE SEE FS |
| 713.13(2) IF WORK HAS NO COMMENCED |
| WITHIN 90 DAYS OF RECORDING, NOC |
| EXPIRES. |
| |
| PLEASE SEE SOME OF THESE ITEMS HAVE |
| BEEN REDLINED AT LOCATIONS OF NOTES. |
| |
| PLEASE BE SURE ANY OLD/VOIDED SHEETS ARE |
| REMOVED AND ONLY INSERT NEW REVISED |
| SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| STAMPING. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |