Plan Review Notes
Plan Review Notes For Permit 04120830
Permit Number 04120830
Review Stop E
Sequence Number 2
Notes
Date Text
2005-07-11 00:00:00********* UNSAT 2ND REVIEW **********
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
 1)NOTE: NOTE #1, OK, AIC CALCS SHOWN.
  
 2)NOTE: NOTE #2 NO,
 PLEASE SEE 310.16,240.4, AND 250.66 FOR
 SIZING.
  
 3)NOTE: NOTE #3 OK.
  
 4)NOTE: NOTE #4 NO, SERVICE IS NOW SHOWN
 TO BE LOCATED ON FRONT BLDG, HOWEVER NO
 INFORMATION FOR MAINS AT DETACHED BLDG.
 PLEASE SEE 225.32, 225.34
 GROUNDING PER 250.32
  
 5)NOTE: NOTE #5 OK, HOWEVER PLEASE SEE
 NEWNOTE;
  
 6)NOTE: NOTE #6 NO, CU'S AND CU'S DISC'S
 SHOWN, HOWEVER PLEASE SEE AHU'S AND
 MISSING AHU'S DISC'S.
  
 7)NOTE: NOTE #7 NO, PLEASE SEE PREVIOUS.
 310.16,240.4
  
 8)NOTE: NOTE #8 OK.
 SEE NOTE #4 FOR GROUNDING AT DETACHED
 BLDGS.
  
 9)NOTE: NOTE #9 OK, HOWEVER PLEASE SEE
 NOTE MENTIONS DEVICES TO BE ARC FAULT
 TYPE? PLEASE SEE THESE DEVICES ARE NOT
 MADE AS ARC FAULT PROTECTIVE TYPES.
 PLEASE SEE 210.12 UNDER 2002 NEC, THIS
 REQUIRES THE ENTIRE BRANCH CIRCUIT TO
 HAVE ARC FAULT PROTECTION. THE BREAKER
 AT PANEL IS THE ONLY WAY ARC FAULT
 PROTECTION CAN BE PROVIDED.
  
 10)NOTE: NOTE #10 OK.
  
 11)NOTE: NOTE #11 OK.
  
 NEW NOTES.
  
 1)NOTE: PLEASE SEE MISSING KITCHEN
 COUNTERSPACE GFI PER 210.52C1, PLEASE
 SEE LOWERE AND UPPER UNITS.
  
 2)NOTE: PLEASE SEE MISSING SD EITHER
 INSIDE OR OUTSIDE BEDRM #1 ON FIRST FLR
 UNIT. PLEASE SEE NFPA-72 8-1.4.1.6.2,
 WHICH REQUIRES SD'S IN THE IMMEDIATE
 VICINITY OUTSIDE BEDRMS.
  
 3)NOTE: PLEASE SEE MISSING RECEPT FOR 2'
 OF WALL SPACE IN LIV RM FIRST FLR.
 210.52
  
 4)NOTE: PLEASE SEE ANY HAND WRITTEN
 CHANGES TO PLANS AND SCOPE SHOULD BE
 SIGNED AND DATED BY ENGINEER ALSO. FS
 471.025
  
 5)NOTE: PLEASE SEE COPY OF FS
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSSIONAL(S) AND PLANS WITH REPEAT
 COMMENTS THREE OR MORE TIMES. THIS IS A
 NOTICE ONLY GIVEN AT THIS TIME.
  
 6)NOTE: PLEASE SEE NOC HAS EXPIRED AND
 NEEDS TO BE RE-RECORDED. PLEASE SEE FS
 713.13(2) IF WORK HAS NO COMMENCED
 WITHIN 90 DAYS OF RECORDING, NOC
 EXPIRES.
  
 PLEASE SEE SOME OF THESE ITEMS HAVE
 BEEN REDLINED AT LOCATIONS OF NOTES.
  
 PLEASE BE SURE ANY OLD/VOIDED SHEETS ARE
 REMOVED AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]