Plan Review Notes
Plan Review Notes For Permit 04120830
Permit Number 04120830
Review Stop B
Sequence Number 2
Notes
Date Text
2005-07-21 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2001
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2001
  
 THE FOLLOWING COMMENTS ARE FROM THE
 PREVIOUS REVIEW.
  
 1.)SEE PROPERTY APPRAISER VALUATION
 ATTACHED.THIS IS AN OVER 50%
 IMPROVEMENT AND MUST COMPLY WITH
 FBC3401.7.2.6.THIS SECTION AFFECTS
 OTHER COMMENTS ON THIS LIST. (WAS
 ACKNOWLEDGED.)
  
 2.)PROVIDE A COPY OF THE SURVEY FOR
 THIS PROPERTY.
  
 THE SURVEY SHOWS A 1 STORY GARAGE ON THE
 PROPERTY LINE.PROVIDE INFORMATION IN
 REGARDS TO THIS BUILDING AND SHOW FBC
 TABLE 600 COMPLIANCE.
  
 3.)THIS APPEARS TO BE TWO UNITS; ONE
 UPSTAIRS, ONE DOWNSTAIRS.2ND FLOOR IS
 TO BE IMPACT GLASS, CITY OF WEST PALM
 BEACH IMPLEMENTATION STANDARD FOR
 HURRICANE MISSILE IMPACT PROTECTION,
 ITEM #13, SEE ATTACHED.SUBMIT A
 HURRICANE INSTALLATION PLAN INCLUDING
 WHERE THE SHUTTERS WILL BE STORED FOR
 SHUTTERS USED ON THE FIRST FLOOR.
  
 THIS WAS ADDRESSED BY CHANGING THE
 SECOND FLOOR TO IMPACT AND A NOTE
 STATING THAT THE FIRST FLOOR SHUTTERS
 WOULD BE STORED IN THE UTILITY ROOM
 BELOW THE STAIRS.ONLY THE BUILDING
 OFFICIAL CAN APPROVE THE USE OF SHUTTERS
 ON A COMMERCIAL BUILDING.PLEASE SUBMIT
 A HURRICANE SHUTTER INSTALLATION PLAN
 FOR REVIEW.THIS IS TO INCLUDE ALL
 PERTINENT INFORMATION SUCH AS STORAGE
 LOCATION, SIZE OF STORAGE AREA, WHERE
 THEY ARE STORED IN THAT AREA, HOW THEY
 ARE SECURED IN THAT LOCATION; WHO IS TO
 INSTALL THEM; TIME ESTIMATE FOR
 INSTALLATION; WHEN THE SHUTTERS WILL BE
 INSTALLED, ETC.THIS MAY BE SUBMITTED
 SEPARATELY FROM PLAN REVIEW (NO FEE).
  
 4.)THE BALCONY (MEANS OF EGRESS FOR
 2ND FLOOR UNIT) IS TO COMPLY WITH
 FBC1014.1.SHOW FIRE RESISTANCE (UL
 ASSEMBLY OR CALCULATED FBC CHAPTER 7),
 PROVIDE DOOR FIRE RATING INFORMATION.
  
 THE FIRE RATING FOR THE DOOR WAS
 PROVIDED.I BELIEVE THAT THIS WAS
 ADDRESSED BY SHOWING TWO LAYERS OF
 DRYWALL ON THE CEILING OF THE FIRST
 FLOOR UNIT.PROVIDE CALCULATED FIRE
 RESISTANCE FOR THE FLOOR/CEILING
 ASSEMBLY FBC709 (EACH COMPONENT AND
 TIME, SHOW TOTAL).
  
 5.)THE EXTERIOR STAIR IS TO COMPLY
 WITH FBC1006.2.4.SHOW FIRE RESISTANCE
 OF THE WALL.OPENINGS WITHIN 10' ARE
 TO BE 3/4 HR.INDICATE ON THE PLAN.
  
 FIRE RESISTANCE OF THE WALL REQUIRED BY
 FBC1006.2.4 WAS NOT SHOWN.THERE IS A
 NOTE ON THE PLAN REGARDING OPENINGS.IT
 IS THE RESPONSIBILITY OF THE DESIGNER TO
 DETERMINE WHICH OPENINGS ARE TO BE
 PROTECTED.INDICATE ON THE ELEVATIONS,
 FLOOR PLAN OR A SCHEDULE. ALSO INCLUDE
 THE REAR BUILDING.SHOW RATED WALL
 REQUIREMENT ON THE FLOOR PLAN AS WELL AS
 A DETAIL SHOWING HOW IT COMPLIES.
  
 6.)THIS PROPERTY IS ON THE DEMO LIST.
 AN ORDER FROM THE BOARD FOR REPAIRS
 MUST BE GRANTED BEFORE A PERMIT CAN BE
 ISSUED.
  
 AN ORDER WAS GRANTED, BUT IT IS MY
 UNDERSTANDING THAT ALL BUILDINGS ARE TO
 BE BROUGHT TO 100% CODE COMPLIANCE.THE
 REAR BUILDING AND GARAGE ARE ALSO TO BE
 INCLUDED IN THIS PERMIT, ALTHOUGH A
 SEPARATE PERMIT NUMBERS AND APPLICATION
 FORMS WILL BE REQUIRED.PLEASE CONTACT
 ME IF YOU FEEL THAT MY UNDERSTANDING IS
 NOT CORRECT.
  
 7.)SHEATHING NAILING IS TO COMPLY
 WITH CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC TABLE 2306.1.SEE ATTACHED.
  
 NOT ADDRESSED.FBC*TABLE 2306.1.NON
 COMPLIANT FOR ZONE 3 (4/6, NOT 6/6).
  
 8.)PROVIDE DESIGN PRESSURES FOR THE
 ROOF.
  
 PLEASE CLARIFY HOW YOU HAVE DETERMINED
 THE PRESSURE TO BE +-38.87, FBC1606.2B.
 SHOULDN?T THIS BE -89?
  
 9.)FOR THE MODIFIED ROOF, INDICATE
 WHICH METHOD OF INSTALLATION YOU ARE
 USING.
  
 THIS SHOULD BE DONE BY CHOOSING ONE OF
 THE APPROVED ASSEMBLIES ON THE PRODUCT
 APPROVAL.
  
 10.)SPECIFY THE STRAPS.FASTENING
 MUST BE CONSISTENT WITH THE
 MANUFACTURER'S SPECIFICATIONS.
  
 SOME STRAPS WERE SPECIFIED, OTHERS HAD
 ONLY A SIZE.THIS IS A STRUCTURAL
 COMPONENT REQUIRING TESTING OR
 ENGINEERING AND STATE OR LOCAL PRODUCT
 APPROVAL FAC9B72.SPECIFY STRAP,
 MANUFACTURER AND NUMBER, AND FASTENING
 IN ACCORDANCE WITH MANUFACTURER
 INSTRUCTIONS.
  
 NEW COMMENTS
  
 11.)BATHROOM DOOR ON THE FIRST FLOOR
 IS TO COMPLY WITH FBC11-11(1), CLEAR
 OPENING OF AT LEAST 29IN.
  
 12.)THE ELEVATIONS AND WALL SECTION DO
 NOT MATCH.IS THERE A PARAPET WALL?IF
 THERE IS, SHOW DRAINAGE FBC1503.4.
  
 13.)THREE DIFFERENT NOAS ARE INCLUDED
 IN THE DOOR PRODUCT APPROVAL PACKAGE
 SUBMITTED.PLEASE SUBMIT ONLY THE DOOR
 YOU ARE USING.
  
 14.)PROVIDE ENERGY CALCS FOR THE REAR
 BUILDING.
  