Date |
Text |
2005-07-21 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2001 |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| TO THE FBC2001 |
| |
| THE FOLLOWING COMMENTS ARE FROM THE |
| PREVIOUS REVIEW. |
| |
| 1.)SEE PROPERTY APPRAISER VALUATION |
| ATTACHED.THIS IS AN OVER 50% |
| IMPROVEMENT AND MUST COMPLY WITH |
| FBC3401.7.2.6.THIS SECTION AFFECTS |
| OTHER COMMENTS ON THIS LIST. (WAS |
| ACKNOWLEDGED.) |
| |
| 2.)PROVIDE A COPY OF THE SURVEY FOR |
| THIS PROPERTY. |
| |
| THE SURVEY SHOWS A 1 STORY GARAGE ON THE |
| PROPERTY LINE.PROVIDE INFORMATION IN |
| REGARDS TO THIS BUILDING AND SHOW FBC |
| TABLE 600 COMPLIANCE. |
| |
| 3.)THIS APPEARS TO BE TWO UNITS; ONE |
| UPSTAIRS, ONE DOWNSTAIRS.2ND FLOOR IS |
| TO BE IMPACT GLASS, CITY OF WEST PALM |
| BEACH IMPLEMENTATION STANDARD FOR |
| HURRICANE MISSILE IMPACT PROTECTION, |
| ITEM #13, SEE ATTACHED.SUBMIT A |
| HURRICANE INSTALLATION PLAN INCLUDING |
| WHERE THE SHUTTERS WILL BE STORED FOR |
| SHUTTERS USED ON THE FIRST FLOOR. |
| |
| THIS WAS ADDRESSED BY CHANGING THE |
| SECOND FLOOR TO IMPACT AND A NOTE |
| STATING THAT THE FIRST FLOOR SHUTTERS |
| WOULD BE STORED IN THE UTILITY ROOM |
| BELOW THE STAIRS.ONLY THE BUILDING |
| OFFICIAL CAN APPROVE THE USE OF SHUTTERS |
| ON A COMMERCIAL BUILDING.PLEASE SUBMIT |
| A HURRICANE SHUTTER INSTALLATION PLAN |
| FOR REVIEW.THIS IS TO INCLUDE ALL |
| PERTINENT INFORMATION SUCH AS STORAGE |
| LOCATION, SIZE OF STORAGE AREA, WHERE |
| THEY ARE STORED IN THAT AREA, HOW THEY |
| ARE SECURED IN THAT LOCATION; WHO IS TO |
| INSTALL THEM; TIME ESTIMATE FOR |
| INSTALLATION; WHEN THE SHUTTERS WILL BE |
| INSTALLED, ETC.THIS MAY BE SUBMITTED |
| SEPARATELY FROM PLAN REVIEW (NO FEE). |
| |
| 4.)THE BALCONY (MEANS OF EGRESS FOR |
| 2ND FLOOR UNIT) IS TO COMPLY WITH |
| FBC1014.1.SHOW FIRE RESISTANCE (UL |
| ASSEMBLY OR CALCULATED FBC CHAPTER 7), |
| PROVIDE DOOR FIRE RATING INFORMATION. |
| |
| THE FIRE RATING FOR THE DOOR WAS |
| PROVIDED.I BELIEVE THAT THIS WAS |
| ADDRESSED BY SHOWING TWO LAYERS OF |
| DRYWALL ON THE CEILING OF THE FIRST |
| FLOOR UNIT.PROVIDE CALCULATED FIRE |
| RESISTANCE FOR THE FLOOR/CEILING |
| ASSEMBLY FBC709 (EACH COMPONENT AND |
| TIME, SHOW TOTAL). |
| |
| 5.)THE EXTERIOR STAIR IS TO COMPLY |
| WITH FBC1006.2.4.SHOW FIRE RESISTANCE |
| OF THE WALL.OPENINGS WITHIN 10' ARE |
| TO BE 3/4 HR.INDICATE ON THE PLAN. |
| |
| FIRE RESISTANCE OF THE WALL REQUIRED BY |
| FBC1006.2.4 WAS NOT SHOWN.THERE IS A |
| NOTE ON THE PLAN REGARDING OPENINGS.IT |
| IS THE RESPONSIBILITY OF THE DESIGNER TO |
| DETERMINE WHICH OPENINGS ARE TO BE |
| PROTECTED.INDICATE ON THE ELEVATIONS, |
| FLOOR PLAN OR A SCHEDULE. ALSO INCLUDE |
| THE REAR BUILDING.SHOW RATED WALL |
| REQUIREMENT ON THE FLOOR PLAN AS WELL AS |
| A DETAIL SHOWING HOW IT COMPLIES. |
| |
| 6.)THIS PROPERTY IS ON THE DEMO LIST. |
| AN ORDER FROM THE BOARD FOR REPAIRS |
| MUST BE GRANTED BEFORE A PERMIT CAN BE |
| ISSUED. |
| |
| AN ORDER WAS GRANTED, BUT IT IS MY |
| UNDERSTANDING THAT ALL BUILDINGS ARE TO |
| BE BROUGHT TO 100% CODE COMPLIANCE.THE |
| REAR BUILDING AND GARAGE ARE ALSO TO BE |
| INCLUDED IN THIS PERMIT, ALTHOUGH A |
| SEPARATE PERMIT NUMBERS AND APPLICATION |
| FORMS WILL BE REQUIRED.PLEASE CONTACT |
| ME IF YOU FEEL THAT MY UNDERSTANDING IS |
| NOT CORRECT. |
| |
| 7.)SHEATHING NAILING IS TO COMPLY |
| WITH CITY OF WEST PALM BEACH AMENDMENTS |
| TO THE FBC TABLE 2306.1.SEE ATTACHED. |
| |
| NOT ADDRESSED.FBC*TABLE 2306.1.NON |
| COMPLIANT FOR ZONE 3 (4/6, NOT 6/6). |
| |
| 8.)PROVIDE DESIGN PRESSURES FOR THE |
| ROOF. |
| |
| PLEASE CLARIFY HOW YOU HAVE DETERMINED |
| THE PRESSURE TO BE +-38.87, FBC1606.2B. |
| SHOULDN?T THIS BE -89? |
| |
| 9.)FOR THE MODIFIED ROOF, INDICATE |
| WHICH METHOD OF INSTALLATION YOU ARE |
| USING. |
| |
| THIS SHOULD BE DONE BY CHOOSING ONE OF |
| THE APPROVED ASSEMBLIES ON THE PRODUCT |
| APPROVAL. |
| |
| 10.)SPECIFY THE STRAPS.FASTENING |
| MUST BE CONSISTENT WITH THE |
| MANUFACTURER'S SPECIFICATIONS. |
| |
| SOME STRAPS WERE SPECIFIED, OTHERS HAD |
| ONLY A SIZE.THIS IS A STRUCTURAL |
| COMPONENT REQUIRING TESTING OR |
| ENGINEERING AND STATE OR LOCAL PRODUCT |
| APPROVAL FAC9B72.SPECIFY STRAP, |
| MANUFACTURER AND NUMBER, AND FASTENING |
| IN ACCORDANCE WITH MANUFACTURER |
| INSTRUCTIONS. |
| |
| NEW COMMENTS |
| |
| 11.)BATHROOM DOOR ON THE FIRST FLOOR |
| IS TO COMPLY WITH FBC11-11(1), CLEAR |
| OPENING OF AT LEAST 29IN. |
| |
| 12.)THE ELEVATIONS AND WALL SECTION DO |
| NOT MATCH.IS THERE A PARAPET WALL?IF |
| THERE IS, SHOW DRAINAGE FBC1503.4. |
| |
| 13.)THREE DIFFERENT NOAS ARE INCLUDED |
| IN THE DOOR PRODUCT APPROVAL PACKAGE |
| SUBMITTED.PLEASE SUBMIT ONLY THE DOOR |
| YOU ARE USING. |
| |
| 14.)PROVIDE ENERGY CALCS FOR THE REAR |
| BUILDING. |
| |