Date |
Text |
2004-12-23 00:00:00 | **************** UNSAT ************* |
| |
| |
| 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING |
| INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO |
| BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9/215.5 |
| |
| 2)NOTE: PLEASE SEE 250.66 FOR SIZING OF |
| GROUNDING ELECTRODE CONDUCTOR. |
| |
| 3)NOTE: PLEASE CLARIFY WHICH LOCATION |
| SERVICE IS GOING TO BE? |
| SHOWN ON REAR BLDG AND MAIN FRONT |
| BLDG?? |
| PLEASE SEE 230.72 FOR REQUIRED GROUPING |
| OF MAINS. |
| |
| 4)NOTE: PLEASE SEE 225.31,32.36 FOR |
| MEANS OF DISC AT DETACHED BLDGS. PLEASE |
| ALSO SEE 250.32 FOR GROUNDING. |
| |
| |
| |
| 5)NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| KITCHEN COUNTERSPACE AS GFI/GFI |
| PROTECT- |
| -ED PER 210.8A-6 |
| |
| 6)NOTE: PLEASE SHOW ALL AC/ EQUIPMENT |
| ON |
| PLANS ALONG WITH REQUIRED DISC'S, |
| RECEPTS PER . 215.5,440.11,210.63 |
| |
| 7)NOTE: PLEASE SEE 310.16 FOR SIZING OF |
| SEC'S PER 240.4B |
| |
| 8)NOTE: PLEASE SEE MISSING EQUIPMENT |
| GROUNDIG FROM MAINS TO PANELS. |
| LOCAL AMENDMENTS: |
| |
| 9)NOTE:PLEASE SEE 2002 NEC 210.12 FOR |
| ARC FAULT PROTECTION. |
| |
| 10)NOTE: PLEASE SEE FAC 61G15-23.002 |
| FOR |
| MISSING REQUIRED INFORMATION ON TITLE |
| BLOCK. |
| REQUIRED UNDER FS 471.023 |
| |
| 11)NOTE: PLEASE SEE #12 AWG ON 30A OCP |
| FOR WATER HEATER. |
| PLEASE SEE 310.16/240.4B |
| |
| PLEASE SEE OTHER POSSIBLE COMMENTS FROM |
| OTHER REVIEWERS WHICH MAY AFFECT |
| ELECTRICAL PLANS. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO TWO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| ONE SET OF OLD SHEETS SHOULD BE |
| SUBMITTED FOR REFERENCE. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |
| [email protected] |