2004-12-28 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| |
| 1.)SEE PROPERTY APPRISER VALUATION |
| ATTACHED.THIS IS AN OVER 50% |
| IMPROVEMENT AND MUST COMPLY WITH |
| FBC3401.7.2.6.THIS SECTION AFFECTS |
| OTHER COMMENTS ON THIS LIST. |
| |
| 2.)PROVIDE A COPY OF THE SURVEY FOR |
| THIS PROPERTY. |
| |
| 3.)THIS APPEARS TO BE TWO UNITS; ONE |
| UPSTAIRS, ONE DOWNSTAIRS.2ND FLOOR IS |
| TO BE IMPACT GLASS, CITY OF WEST PALM |
| BEACH IMPLEMENTATION STANDARD FOR |
| HURRICANE MISSILE IMPACT PROTECTION, |
| ITEM #13, SEE ATTACHED.SUBMIT A |
| HURRICANE INSTALLATION PLAN INCLUDING |
| WHERE THE SHUTTERS WILL BE STORED FOR |
| SHUTTERS USED ON THE FIRST FLOOR. |
| |
| 4.)THE BALCONY (MEANS OF EGRESS FOR |
| 2ND FLOOR UNIT) IS TO COMPLY WITH |
| FBC1014.1.SHOW FIRE RESISTANCE (UL |
| ASSEMBLY OR CALCULATED FBC CHAPTER 7), |
| PROVIDE DOOR FIRE RATING INFORMATION. |
| |
| 5.)THE EXTERIOR STAIR IS TO COMPLY |
| WITH FBC1006.2.4.SHOW FIRE RESISTANCE |
| OF THE WALL.OPENINGS WITHIN 10' ARE |
| TO |
| BE 3/4 HR.INDICATE ON THE PLAN. |
| |
| 6.)PROVIDE TENANT SEPARATION FIRE |
| RESISTANCE INFORMATION FBC704.3. |
| |
| 7.)A 24 WINDOW DOES NOT COMPLY WITH |
| EMERGENCY EGRESS REQUIREMENTS |
| FBC1005.4. |
| |
| 8.)THIS PROPERTY IS ON THE DEMO LIST. |
| AN ORDER FROM THE BOARD FOR REPAIRS |
| MUST |
| BE GRANTED BEFORE A PERMIT CAN BE |
| ISSUED. |
| |
| 9.)PROVIDE MULLION PRODUCT APPROVALS. |
| |
| 10.) PROVIDE AREA CALCULATIONS |
| (EXISTING, PROPOSED, NEW TOTAL).THIS |
| PROJECT INVOLVES AN ADDITION. |
| |
| 11.)PROVIDE ELEVATIONS. |
| |
| 12.)IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY.THE PLANS MUST BE |
| STAMPED |
| AND THE RECEIPT ATTACHED TO THE |
| APPLICATION. |
| |
| 13.)SHEATHING NAILING IS TO COMPLY |
| WITH CITY OF WEST PALM BEACH AMENDMENTS |
| TO THE FBC TABLE 2306.1.SEE ATTACHED. |
| |
| 14.)PROVIDE DESIGN PRESSURES FOR THE |
| ROOF. |
| |
| 15.)FOR THE MODIFIED ROOF, INDICATE |
| WHICH METHOD OF INSTALLATION YOU ARE |
| USING. |
| |
| 16.)HOW HAVE YOU DETERMINED THE |
| DESIGN |
| PRESSURE FOR THE WINDOWS?FBC TABLE |
| 1606.2B, 140MPH, EXPOSURE B, ZONE 5 |
| LESS |
| THAN 10SF HAS A REQUIREMENT OF -47.2. |
| YOU HAVE DECLARED AN EXPOSURE C, SO THE |
| NEGATIVE PRESSURE SHOULD BE -67.2. |
| YOUR |
| PLAN STATES -44. |
| |
| 17.)SPECIFY THE STRAPS.FASTENING |
| MUST |
| BE CONSISTENT WITH THE MANUFACTURER'S |
| SPECIFICATIONS. |
| |
| 18.)ALL INFORMATION REQUIRED BY |
| FAC61G15-23.002 IS TO BE ON THE TITLE |
| BLOCK.CA NUMBER REQUIRED. |