Plan Review Notes
Plan Review Notes For Permit 04120811
Permit Number 04120811
Review Stop E
Sequence Number 1
Notes
Date Text
2004-12-22 00:00:00********* UNSAT ************
  
 1)NOTE: PLEASE PROVIDE A PANEL SCHEDULE
 SHOWING THE MIN ELECTRICAL CIRCUITS
 REQUIRED UNDER 2002 NEC.
 210.52
 210.11
 220
 PLEASE SHOW AWG AND OCP.
 PLEASE SHOW WIRING FOR A/C ON PLANS AND
 SHOW LOCATIONS OF A/C EQUIPMENT/DISC'S.
 440.11
  
 2)NOTE: PLANS MUST CONTAIN THE PRINTED
 NAME AND SIGNATURE OF THE PERSON MORE
 RESPONSIBLE FOR PLANS.
 FBC 104.2.1
  
 PLEASE SUBMIT THE ABOVEINFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]