Plan Review Notes For Permit 04120811 |
Permit Number |
04120811 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-12-22 00:00:00 | ********* UNSAT ************ | | | | 1)NOTE: PLEASE PROVIDE A PANEL SCHEDULE | | SHOWING THE MIN ELECTRICAL CIRCUITS | | REQUIRED UNDER 2002 NEC. | | 210.52 | | 210.11 | | 220 | | PLEASE SHOW AWG AND OCP. | | PLEASE SHOW WIRING FOR A/C ON PLANS AND | | SHOW LOCATIONS OF A/C EQUIPMENT/DISC'S. | | 440.11 | | | | 2)NOTE: PLANS MUST CONTAIN THE PRINTED | | NAME AND SIGNATURE OF THE PERSON MORE | | RESPONSIBLE FOR PLANS. | | FBC 104.2.1 | | | | PLEASE SUBMIT THE ABOVEINFORMATION | | FOR REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|