2005-03-01 00:00:00 | DENIED |
| REFERENCE: FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| |
| FROM PREVIOUS REVIEW: |
| SUBMIT A DETAIL FOR THE KITCHEN SINK |
| SHOWING COMPLIANCE WITH THE FOLLOWING: |
| A) KNEE CLEARANCE 11-4.24.3 |
| B) SINK DEPTH 11-4.24.4 |
| C) CLEAR FLOOR SPACE 11-4.24.5 (THE |
| CLEAR FLOOR SPACE SHALL BE PROVIDED IN |
| FRONT OF A SINK TO ALLOW FORWARD |
| APPROACH. THE CLEAR FLOOR SPACE SHALL BE |
| ON AN ACCESSIBLE ROUTE AND SHALL EXTEND |
| A MAXIMUM OF 19" UNDERNEATH THE SINK). |
| (SEE FIGURE 32). PARALLEL APPROACH IS |
| NOT APPROVED. |
| D) EXPOSED PIPES AND SURFACES 11-4.24.6 |
| E) FAUCETS 11-4.24.7 |
| *****THIS INFORMATION SHALL BE INCLUDED |
| ON THE PLANS. SUCH INFORMATION SHALL BE |
| SPECIFIC, AND THE TECHNICAL CODES SHALL |
| NOT BE CITED AS A WHOLE OR IN PART, NOR |
| SHALL THE TERM "LEGAL" OR ITS EQUIVALENT |
| BE USED AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION. SECTION 104.2.1.***** |
| 2) SUBMIT A DETAIL FOR THE TOILET ROOMS |
| SHOWING THE FOLLOWING INFORMATION: |
| B) TOILET TO BE 18" OFF THE WALL TO THE |
| CENTERLINE OF THE FIXTURE. FIG. 28 |
| D) GRAB BARS 11-4.16.4 GRAB BARS FOR |
| WATER CLOSETS NOT LOCATED IN STALLS |
| SHALL COMPLY WITH 11-4.26 AND FIGURE 29. |
| FLOOR MOUNTED GRAB BARS ARE NOT APPROVED |
| PER THIS SECTION OF THE CODE. |
| E) FLUSH CONTROLS 11-4.16.5 - NO |
| RESPONSE TO THIS REQUEST NOTED. |
| G) EXPOSED PIPES & SURFACES 11-4.19.4 - |
| NO RESPONSE TO THIS REQUEST NOTED. |
| H) FAUCET 11-4.19.5 |
| *************NEW COMMENT********* |
| SEE SHEET CONCERNING DESIGN PROFESSIONAL |
| AND FLA. STATUTE 553.80(2)(B) SUBMITTED |
| BY THE STRUCTURAL PLAN REVIEWER. |
| |