Plan Review Notes
Plan Review Notes For Permit 04120738
Permit Number 04120738
Review Stop P
Sequence Number 2
Notes
Date Text
2005-03-01 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 FROM PREVIOUS REVIEW:
 SUBMIT A DETAIL FOR THE KITCHEN SINK
 SHOWING COMPLIANCE WITH THE FOLLOWING:
 A) KNEE CLEARANCE 11-4.24.3
 B) SINK DEPTH 11-4.24.4
 C) CLEAR FLOOR SPACE 11-4.24.5 (THE
 CLEAR FLOOR SPACE SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD
 APPROACH. THE CLEAR FLOOR SPACE SHALL BE
 ON AN ACCESSIBLE ROUTE AND SHALL EXTEND
 A MAXIMUM OF 19" UNDERNEATH THE SINK).
 (SEE FIGURE 32). PARALLEL APPROACH IS
 NOT APPROVED.
 D) EXPOSED PIPES AND SURFACES 11-4.24.6
 E) FAUCETS 11-4.24.7
 *****THIS INFORMATION SHALL BE INCLUDED
 ON THE PLANS. SUCH INFORMATION SHALL BE
 SPECIFIC, AND THE TECHNICAL CODES SHALL
 NOT BE CITED AS A WHOLE OR IN PART, NOR
 SHALL THE TERM "LEGAL" OR ITS EQUIVALENT
 BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION. SECTION 104.2.1.*****
 2) SUBMIT A DETAIL FOR THE TOILET ROOMS
 SHOWING THE FOLLOWING INFORMATION:
 B) TOILET TO BE 18" OFF THE WALL TO THE
 CENTERLINE OF THE FIXTURE. FIG. 28
 D) GRAB BARS 11-4.16.4 GRAB BARS FOR
 WATER CLOSETS NOT LOCATED IN STALLS
 SHALL COMPLY WITH 11-4.26 AND FIGURE 29.
 FLOOR MOUNTED GRAB BARS ARE NOT APPROVED
 PER THIS SECTION OF THE CODE.
 E) FLUSH CONTROLS 11-4.16.5 - NO
 RESPONSE TO THIS REQUEST NOTED.
 G) EXPOSED PIPES & SURFACES 11-4.19.4 -
 NO RESPONSE TO THIS REQUEST NOTED.
 H) FAUCET 11-4.19.5
 *************NEW COMMENT*********
 SEE SHEET CONCERNING DESIGN PROFESSIONAL
 AND FLA. STATUTE 553.80(2)(B) SUBMITTED
 BY THE STRUCTURAL PLAN REVIEWER.
  