Plan Review Notes
Plan Review Notes For Permit 04120738
Permit Number 04120738
Review Stop B
Sequence Number 2
Notes
Date Text
2005-02-18 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS LIST, PROVIDE DETAILS
 FOR THE GRAB BARS TO SHOW COMPLIANCE
 WITH FBC CHAPTER 11.FBC11-4.17.6
 REQUIRES GRAB BARS IN COMPLIANCE WITH
 FBC CHAPTER 11 FIGURE 30(A) THROUGH (D).
 THE DETAIL PROVIDED FOR THE SIDE GRAB
 BAR DOES NOT GIVE A LENGTH.A GRAB BAR
 AT THE BACK OF THE TOILET IS SHOWN
 GRAPHICALLY ON THE FLOOR PLAN BUT DOES
 NOT APPEAR COMPLIANT WITH FIGURE 30.
 THE REAR GRAB BAR IS NOT SHOWN AT ALL ON
 SECTION B.
  
 2.)SHOW KNEE CLEARANCE FOR THE SINK,
 FBC11-4.24.3.THE PIPES ARE TO BE
 INSULATED, FBC11-4.24.6.NONE SHOWN ON
 THE DETAIL.
  
 3.)CONTACT PALM BEACH COUNTY IMPACT
 FEES TO DETERMINE POSSIBLE IMPACT FEES
 DUE (CHANGE OF USE).233-5025.THE
 PLANS ARE TO BE STAMPED AND THE RECEIPT
 ATTACHED TO THE APPLICATION.
  
 4.)SEE ATTACHED FS553.80(2)(B).