2005-08-01 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THERE IS NO GROUND ROD IN THE
 GROUNDING ELECTRODE SYSTEM PER
 250.52(A)(5).
  
 2} THERE ARE 3 SMALL APPLIANCE CIRCUITS
 IN THE CALCULATIONS, BUT ONLY ONE ON THE
 PANEL SCHEDULE. SEE 210.11(C)(3) FOR
 REQUIREMENTS.
  
 3} THE SMOKE DETECTOR IN THE BATHROOM IS
 IN VIOLATION OF NFPA-72 ARTICLE 8-1.4.2.
  
 4} THE RECEPTACLE FOR THE "IRRIGATION"
 SYSTEM MUST BE GFI PROTECTED PER
 210.8(A)(3).
  
 5} PLEASE NOTE THAT ONLY 1 THREE WAY
 SWITCH WAS ADDED TO THE DINING ROOM
 LIGHT REVISION.
  
 6} THE LAST REVISION DATE IN THE TITLE
 BLOCK IS 8-21-04. PLEASE CORRECT SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  