Plan Review Notes For Permit 04120578 |
Permit Number |
04120578 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-08-01 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THERE IS NO GROUND ROD IN THE | | GROUNDING ELECTRODE SYSTEM PER | | 250.52(A)(5). | | | | 2} THERE ARE 3 SMALL APPLIANCE CIRCUITS | | IN THE CALCULATIONS, BUT ONLY ONE ON THE | | PANEL SCHEDULE. SEE 210.11(C)(3) FOR | | REQUIREMENTS. | | | | 3} THE SMOKE DETECTOR IN THE BATHROOM IS | | IN VIOLATION OF NFPA-72 ARTICLE 8-1.4.2. | | | | 4} THE RECEPTACLE FOR THE "IRRIGATION" | | SYSTEM MUST BE GFI PROTECTED PER | | 210.8(A)(3). | | | | 5} PLEASE NOTE THAT ONLY 1 THREE WAY | | SWITCH WAS ADDED TO THE DINING ROOM | | LIGHT REVISION. | | | | 6} THE LAST REVISION DATE IN THE TITLE | | BLOCK IS 8-21-04. PLEASE CORRECT SAME. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | |
|