Plan Review Notes
Plan Review Notes For Permit 04120528
Permit Number 04120528
Review Stop E
Sequence Number 1
Notes
Date Text
2004-12-27 00:00:00*********** UNSAT **********
  
 1)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%.
 230.42,215.3, TEC
  
 2)NOTE: PLEASE CLARIFY NEW OR EXISTING
 GRND FOR TRANSFORMER. 250.30
  
 3)NOTE: PLEASE SEE MISSING INFORMATION
 ON TITLE BLOCK FOR ARCH'S FIRM.
 FAC 61G1-16.004, FS 481.219
 PLEASE SEE THIS IS REQUIRED ON ALL
 SHEETS AND FOR ALL TRADES WHEATHER OR
 NOT COMMENT IS MADE BY OTHER
 REVIEWER(S).
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLYINSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  