Plan Review Notes
Plan Review Notes For Permit 04120452
Permit Number 04120452
Review Stop E
Sequence Number 1
Notes
Date Text
2004-12-10 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR ALL NEW
 SERVICE EQUIPMENT BEING INSTALLED.
 MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9.
  
 2} INDICATE THE GROUNDING ELECTRODE
 CONDUCTOR SIZE PER 250.66.
  
 3} INDICATE SIZE & TYPE OF CONDUIT USED
 FOR RISER AND NIPPLE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026