Plan Review Notes
Plan Review Notes For Permit 04120353
Permit Number 04120353
Review Stop P
Sequence Number 9
Notes
Date Text
2006-07-03 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FHA-98 DESIGN MANUAL
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
  
  
  
  
 7-4A. SHT P2.10 CHANGE 10.3 PTR RISER
 SHOWN IS NOT SHOWN ON THE GROUND FLOOR.
 WHERE DOES THIS RISER TERMINATE? PLEASE
 CLARIFY. SECTION 104.2.1.
 ***THIS SHEET HAS NOT BEEN REVISED AS
 REQUIRED IN THE PROVISO.
  
 8-4A. SHT P2.14 CHANGE 13.1 OFFSET TO
 RISER 10 DOES NOT REFLECT THE FLOOR
 PLAN. PLEASE CORRELATE RISER AND FLOOR
 PLAN. SECTION 104.2.1.
 ***THIS SHEET HAS NOT BEEN REVISED AS
 REQUIRED IN THE PROVISO.
  
 11-4A. SHT P2.35 CHANGE 31.1 OFSET NOT
 SHOWN ON THE RISER DIAGRAM. SECTION
 104.2.1.
 ***THIS SHEET HAS NOT BEEN REVISED AS
 REQUIRED IN THE PROVISO.
  
 14-4A. SHT P2.44 CHANGE 37.4 VENT PIPING
 LAYOUT DOES NOT REFLECT RISERS 10A, 11,
 11A AND 12 AS INDICATED. PLEASE
 CORRELATE RISERS AND FLOOR PLAN. SECTION
 104.2.1.
 ***RESPONSE NOTED, BUT NO VENT FROM
 RISER #11 IS SHOWN ON THE FLOOR PLAN.
  
 19-4A. SHT P3.17 NEW SHEET OFFSET VENTS
 REQUIRED ON RISER 54A AT THE 5TH FLOOR
 OFFSET. SECTIONS 915.2 & 915.3.
 ***RESPONSE NOTED, BUT THE UPPER OFFSET
 VENT IS NOT SHOWN. SECTION 915.2. (ALSO
 SEE RISER #6 UPPER OFFSET VENT NOT
 SHOWN).
  
 2-E SHTS P2.11, P2.12, & P2.15 PAN DRAIN
 SHALL NOT TERMINATE IN THE PARKING
 GARAGE. SECTION 504.8.2. - EXPLAIN HOW
 DRAINING THE PTR DISCHARGE LINE INTO THE
 GARAGE PARKING MEETS THE REQUIREMENT FOR
 A SAFE DISCHARGE. SECTION 604.7.1.
 ***RESPONSE NOTED, BUT PAN DRAIN LINE
 STILL SHOWN DISCHARGING INTO THE PARKING
 GARAGE.
  
 *************REVISION NOTES*************
  
 1. SHT P2.01 FLOOR DRAIN IN EGRESS
 STAIRWELL NOT APPROVED. NFPA 101, 2003
 CHAPTER 7 SECTION 7.1.3.2.1(6).
  
 2. SHT P2.02 FLOOR DRAIN IN EGRESS
 STAIRWELL NOT APPROVED. NFPA 101 SECTION
 7.1.3.2.1(6). - PAN DRAIN TO GARAGE NOT
 APPROVED. SECTION 504.8.2.
  
 3. SHT P2.03 FLOOR DRAIN IN EGRESS
 STAIRWELL NOT APPROVED. NFPA 101 SECTION
 7.1.3.2.1(6). - CLOUD AND NUMBER ALL
 REVISIONS. SECTION 104.2.1.3.
  
 4. SHT P2.04 FLOOR DRAIN IN EGRESS
 STAIRWELL NOT APPROVED. NFPA 101 SECTION
 7.1.3.2.1(6). - PAN DRAIN LINE TO GARAGE
 NOT APPROVED. SECTION 504.8.2.
  
 5. SHT P2.06 FLOOR DRAIN IN EGRESS
 STAIRWELL NOT APPROVED. NFPA 101 SECTION
 7.1.3.2.1(6). - PAN DRAIN LINE TO GARAGE
 NOT APPROVED. SECTION 504.8.2.
  
 6. SHT P2.08 FLOOR DRAIN I EGRESS
 STAIRWELL NOT APPROVED. NFPA 101 SECTION
 7.1.3.2.1(6). - VENT REQUIRED FOR FLOOR
 DRAIN. SECTION 901.2.1.
  
 7. SHT P3.27 FLOOR DRAIN IN EGRESS
 STAIRWELL NOT APPROVED. NFPA 101 SECTION
 7.1.3.2.1(6).
  
 8. SHT P330 2 FLOOR DRAINS IN EGRESS
 STAIRWELL NOT APPROVED. NFPA 101 SECTION
 7.1.3.2.1(6).- VENT REQUIRED FOR FLOOR
 DRAIN AT STAIRWELL #3. SECTION 901.2.1.
  
 9. SHT P3.31 FLOOR DRAIN IN EGRESS
 STAIRWELL NOT APPROVED. NFPA 101 SECTION
 7.1.3.2.1(6).
  
 10. SHT P3.36 FLOOR DRAIN IN EGRESS
 STAIRWELL NOT APPROVED. NFPA 101 SECTION
 7.1.3.2.1(6).
  
 11. THE FOLLOWING SHEETS WERE APPROVED:
 P2.05, P2.07, P2.12, P2.17, P2.26,
 P2.27, P2.28, P2.33, P2.36, P2,39,
 P2.4O, P2.45, P2.51, P2.61, P3.00,
 P3.04, P3.16, P3.18, P3.19, P3.20,
 P3.21, P3.22, P3.23, P3.24, P3.25,
 P3.26, P3.28, P3.29, P3.32, P3.33,
 P3.34, P3.35, P3.37, P3.40, & P3.41
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]