2006-07-03 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 BUILDING |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| FHA-98 DESIGN MANUAL |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUTES |
| |
| |
| |
| |
| |
| 7-4A. SHT P2.10 CHANGE 10.3 PTR RISER |
| SHOWN IS NOT SHOWN ON THE GROUND FLOOR. |
| WHERE DOES THIS RISER TERMINATE? PLEASE |
| CLARIFY. SECTION 104.2.1. |
| ***THIS SHEET HAS NOT BEEN REVISED AS |
| REQUIRED IN THE PROVISO. |
| |
| 8-4A. SHT P2.14 CHANGE 13.1 OFFSET TO |
| RISER 10 DOES NOT REFLECT THE FLOOR |
| PLAN. PLEASE CORRELATE RISER AND FLOOR |
| PLAN. SECTION 104.2.1. |
| ***THIS SHEET HAS NOT BEEN REVISED AS |
| REQUIRED IN THE PROVISO. |
| |
| 11-4A. SHT P2.35 CHANGE 31.1 OFSET NOT |
| SHOWN ON THE RISER DIAGRAM. SECTION |
| 104.2.1. |
| ***THIS SHEET HAS NOT BEEN REVISED AS |
| REQUIRED IN THE PROVISO. |
| |
| 14-4A. SHT P2.44 CHANGE 37.4 VENT PIPING |
| LAYOUT DOES NOT REFLECT RISERS 10A, 11, |
| 11A AND 12 AS INDICATED. PLEASE |
| CORRELATE RISERS AND FLOOR PLAN. SECTION |
| 104.2.1. |
| ***RESPONSE NOTED, BUT NO VENT FROM |
| RISER #11 IS SHOWN ON THE FLOOR PLAN. |
| |
| 19-4A. SHT P3.17 NEW SHEET OFFSET VENTS |
| REQUIRED ON RISER 54A AT THE 5TH FLOOR |
| OFFSET. SECTIONS 915.2 & 915.3. |
| ***RESPONSE NOTED, BUT THE UPPER OFFSET |
| VENT IS NOT SHOWN. SECTION 915.2. (ALSO |
| SEE RISER #6 UPPER OFFSET VENT NOT |
| SHOWN). |
| |
| 2-E SHTS P2.11, P2.12, & P2.15 PAN DRAIN |
| SHALL NOT TERMINATE IN THE PARKING |
| GARAGE. SECTION 504.8.2. - EXPLAIN HOW |
| DRAINING THE PTR DISCHARGE LINE INTO THE |
| GARAGE PARKING MEETS THE REQUIREMENT FOR |
| A SAFE DISCHARGE. SECTION 604.7.1. |
| ***RESPONSE NOTED, BUT PAN DRAIN LINE |
| STILL SHOWN DISCHARGING INTO THE PARKING |
| GARAGE. |
| |
| *************REVISION NOTES************* |
| |
| 1. SHT P2.01 FLOOR DRAIN IN EGRESS |
| STAIRWELL NOT APPROVED. NFPA 101, 2003 |
| CHAPTER 7 SECTION 7.1.3.2.1(6). |
| |
| 2. SHT P2.02 FLOOR DRAIN IN EGRESS |
| STAIRWELL NOT APPROVED. NFPA 101 SECTION |
| 7.1.3.2.1(6). - PAN DRAIN TO GARAGE NOT |
| APPROVED. SECTION 504.8.2. |
| |
| 3. SHT P2.03 FLOOR DRAIN IN EGRESS |
| STAIRWELL NOT APPROVED. NFPA 101 SECTION |
| 7.1.3.2.1(6). - CLOUD AND NUMBER ALL |
| REVISIONS. SECTION 104.2.1.3. |
| |
| 4. SHT P2.04 FLOOR DRAIN IN EGRESS |
| STAIRWELL NOT APPROVED. NFPA 101 SECTION |
| 7.1.3.2.1(6). - PAN DRAIN LINE TO GARAGE |
| NOT APPROVED. SECTION 504.8.2. |
| |
| 5. SHT P2.06 FLOOR DRAIN IN EGRESS |
| STAIRWELL NOT APPROVED. NFPA 101 SECTION |
| 7.1.3.2.1(6). - PAN DRAIN LINE TO GARAGE |
| NOT APPROVED. SECTION 504.8.2. |
| |
| 6. SHT P2.08 FLOOR DRAIN I EGRESS |
| STAIRWELL NOT APPROVED. NFPA 101 SECTION |
| 7.1.3.2.1(6). - VENT REQUIRED FOR FLOOR |
| DRAIN. SECTION 901.2.1. |
| |
| 7. SHT P3.27 FLOOR DRAIN IN EGRESS |
| STAIRWELL NOT APPROVED. NFPA 101 SECTION |
| 7.1.3.2.1(6). |
| |
| 8. SHT P330 2 FLOOR DRAINS IN EGRESS |
| STAIRWELL NOT APPROVED. NFPA 101 SECTION |
| 7.1.3.2.1(6).- VENT REQUIRED FOR FLOOR |
| DRAIN AT STAIRWELL #3. SECTION 901.2.1. |
| |
| 9. SHT P3.31 FLOOR DRAIN IN EGRESS |
| STAIRWELL NOT APPROVED. NFPA 101 SECTION |
| 7.1.3.2.1(6). |
| |
| 10. SHT P3.36 FLOOR DRAIN IN EGRESS |
| STAIRWELL NOT APPROVED. NFPA 101 SECTION |
| 7.1.3.2.1(6). |
| |
| 11. THE FOLLOWING SHEETS WERE APPROVED: |
| P2.05, P2.07, P2.12, P2.17, P2.26, |
| P2.27, P2.28, P2.33, P2.36, P2,39, |
| P2.4O, P2.45, P2.51, P2.61, P3.00, |
| P3.04, P3.16, P3.18, P3.19, P3.20, |
| P3.21, P3.22, P3.23, P3.24, P3.25, |
| P3.26, P3.28, P3.29, P3.32, P3.33, |
| P3.34, P3.35, P3.37, P3.40, & P3.41 |
| |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |